ATV930C16N4F is the standard version without braking chopper from the Altivar Process ATV900 range, sized for 160 kW normal duty / 132 kW heavy duty on a 380–440 V three-phase supply. Nominal output current is 302 A at 2.5 kHz switching frequency for normal duty, dropping to 250 A for heavy-duty applications. The IP21 enclosure is designed for floor-standing installation — no wall-mount brackets here, so plan panel floor space accordingly.
Line and motor connections use M12 bars — torque to manufacturer specifications, not by feel. Control wiring lands on removable screw terminals, 0.5–1.5 mm². Integrated EMC filter covers conducted emissions; the optional EMC plate (sold separately) finishes the shield termination scheme. The drive includes internal 24 V DC supplies for digital inputs (21–27 V for STO and digital inputs, 19–30 V for the reference potentiometer).
This is a catalog-standard Altivar Process drive; sourcing lead times run quoted to order. If you are holding a BOM freeze, this part number is stable. No direct replacement or cross-reference exists within the same ATV930 frame — variants with a braking chopper carry a different order code, so verify your braking resistor requirement before specifying.