Schneider Electric ATV930C20N4F — AC Drive (VFD) 480V

Schneider ATV930C20N4F Altivar Process ATV900, 200 kW, 370 A

MPNATV930C20N4F
Active

Schneider Electric Altivar Process ATV900 variable speed drive, ATV930C20N4F, 380…440 V three-phase, 200 kW normal duty / 160 kW heavy duty, 370 A continuous output at 2.5 kHz, IP21 floor-standing variant without braking chopper.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV930C20N4F — Identification
ParameterValue
Product typeVariable speed drive
Product range / familyAltivar Process ATV900
ATV930C20N4F — Power & Output
ParameterValue
Motor power (kW)200.0 kW for normal duty 160.0 kW for heavy duty
Continuous output current370 A at 2.5 kHz for normal duty 302 A at 2.5 kHz for heavy duty
ATV930C20N4F — Input / Supply
ParameterValue
Rated supply voltage range380...440 V
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm 500 V DC for 1 minute to earth
ATV930C20N4F — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated With EMC plate option
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
ATV930C20N4F — Mechanical & Cooling
ParameterValue
IP degree of protectionIP21
Acoustic noise level70 dB
Assembly / installation styleIn floor-standing enclosure
ATV930C20N4F — Environmental
ParameterValue
Operating ambient temperature-15...40 °C (without derating) 40...50 °C (with derating factor)
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
ATV930C20N4F — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 60204-1 IEC 61800-2 IEC 61800-3 IEC 61800-5-1
ATV930C20N4F — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP

Product details

The ATV930C20N4F is a 380…440 V three-phase drive sized for 200 kW on normal duty (ND) or 160 kW on heavy duty (HD) — verified by the 370 A continuous output at 2.5 kHz (ND) and 302 A at 2.5 kHz (HD). The integrated EMC filter meets IEC 61800-3 for conducted emissions without an external add-on, saving panel space. Control supply is separate from the power stage: digital inputs and STO use a 24 V DC supply (21…27 V), while the reference potentiometer (1…10 kOhm) gets an internal 10.5 V DC ±5 %. The main digital input supply accepts 19…30 V DC. Isolation to earth is tested at 1 MOhm, 500 V DC for 1 minute.

Floor-standing enclosure with IP21 protection; operating position vertical ±10°. Line and motor connections use M12 bar terminals; control wiring uses removable screw terminals (0.5…1.5 mm²). Requires 1300 m³/h of cooling air — ensure adequate ventilation in the enclosure. Three option slots (A, B, C) accept communication modules for PROFIBUS DP V1, PROFINET, DeviceNet, EtherCAT, CANopen, Ethernet Powerlink, plus digital/analog I/O and relay extensions. Slot B also supports encoder interfaces (digital 5/12 V, analog, or resolver). Built-in EtherNet/IP and Modbus TCP on dual-port RJ45, plus Modbus serial. Configurable baud rates: 10 or 100 Mbits for Ethernet, 4.8 kbps or 19200 bit/s for serial. Communication uses half- or full-duplex with autonegotiation.

Frequently asked questions

What are the control supply voltage requirements for the ATV930C20N4F?

The drive supplies an internal 10.5 V DC ±5 % for a reference potentiometer (1 to 10 kOhm). Digital inputs and STO use a separate internal 24 V DC supply (21…27 V). An external 24 V DC supply (19…30 V) is also available for digital inputs.

Does the ATV930C20N4F include an integrated EMC filter?

Yes, the drive has an integrated EMC filter, with an optional EMC plate for enhanced performance. It is designed to meet IEC 61800-3 conducted emission limits without an external filter in most installations.

What motor power does the ATV930C20N4F support?

The ATV930C20N4F is rated for 200 kW in normal duty and 160 kW in heavy duty, at 380…440 V three-phase input.

MPN
ATV930C20N4F