Skip to main content
Schneider Electric ATV950D45N4E — AC Drive (VFD) 480V

Altivar Process ATV950D45N4E VSD, 45 kW, 88 A, IP55

MPNATV950D45N4E
Active

Altivar Process ATV900 series, variable speed drive, ATV950D45N4E, 45 kW normal duty, 88 A continuous output, 380-480 V three-phase, IP55, with integrated brake chopper and EMC filter.

$10,560.16Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV950D45N4E — Identification
ParameterValue
Product typeVariable speed drive
Product range / familyAltivar Process ATV900
ATV950D45N4E — Power & Output
ParameterValue
Motor power (kW)45.0 kW for normal duty 37.0 kW for heavy duty
Continuous output current88 A at 4 kHz for normal duty 74.5 A at 4 kHz for heavy duty
ATV950D45N4E — Input / Supply
ParameterValue
Rated supply voltage range380...480 V
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm 500 V DC for 1 minute to earth
ATV950D45N4E — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated With EMC plate option
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
ATV950D45N4E — Mechanical & Cooling
ParameterValue
Degree of protection (IP)UL type 1
IP degree of protectionIP55
Acoustic noise level69.7 dB
Assembly / installation styleEnclosed
ATV950D45N4E — Environmental
ParameterValue
Operating ambient temperature-15...40 °C (without derating) 40...50 °C (with derating factor)
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
ATV950D45N4E — Approvals
ParameterValue
Certifications & markingCE
Standards complianceUL 508C IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
ATV950D45N4E — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus TCP Modbus serial

Product details

The ATV950D45N4E variable speed drive from the Altivar Process ATV900 series is rated 45 kW for normal duty and 37 kW for heavy duty, with a continuous output current of 88 A at 4 kHz. The 88 A figure governs feeder cable sizing and thermal margin for sustained motor loads. The drive accepts 380-480 V three-phase and is IP55 enclosed for washdown or dusty environments.

Mounting and installation constraints

Mounts wall-vertical within ±10°. Terminal capacity on motor and line side is 35-50 mm² screw terminals. Expect current derating of 1% per 100 m above 1000 m altitude. Vibration resistance 1.5 mm at 2–13 Hz, 1 gn at 13–200 Hz. Shock resistance 15 gn for 11 ms.

Fieldbus and control interfaces

Embedded protocols include EtherNet/IP, Modbus TCP, and Modbus serial. Slot A accepts optional communication modules for Profibus DP, PROFINET, DeviceNet, EtherCAT, CANopen, or Ethernet Powerlink. Digital inputs accept 24 V DC supply (19–30 V external or 21–27 V internal for STO). Internal 10.5 V DC supply for external reference potentiometer (1–10 kOhm).

Frequently asked questions

What are the main electrical ratings for this drive?

It delivers 45 kW for normal duty, 37 kW for heavy duty, with a continuous output of 88 A at 4 kHz switching frequency, on 380-480 V three-phase supply.

Which communication protocols are built in?

EtherNet/IP, Modbus TCP, and Modbus serial are integrated. Additional protocol modules (Profibus, PROFINET, DeviceNet, etc.) can be added via slot A.

What safety and compliance standards does this drive meet?

It complies with UL 508C, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1, among others.

What are the supply voltage options for the digital inputs?

Digital inputs can use an external 24 V DC supply (19–30 V) or the internal 24 V DC supply (21–27 V) which also powers STO. A separate 10.5 V DC supply is provided for an external reference potentiometer.

MPN
ATV950D45N4E