The ATV980C13T4X1 is a Schneider Electric Altivar Process ATV980 regenerative variable speed drive, rated 160/132 kW on 480 V three-phase supply. It ships as a floor-standing compact enclosure with the Spacial SF cabinet, main switch, line choke, and graphical operating panel already fitted — essentially a pre-kitted regenerative drive package for asynchronous or synchronous motors. The IP23 rating (IEC 61800-5-1) means it handles indoor environments with some falling water or dust ingress; forced convection cooling keeps it running without a fan filter change schedule. Supply frequency is 50...60 Hz ±5 %, so it lands on either 50 Hz or 60 Hz networks without reconfiguration.
The 480 V ±10 % supply voltage covers 432–528 VAC — standard for North American 480 V three-phase and European 400 V networks (the drive will run on 400 V within tolerance). The 50...60 Hz ±5 % range means it accepts 47–63 Hz, so it works on 50 Hz or 60 Hz grids without a hardware change. The IP23 enclosure is not sealed against hose-down; it's for indoor installation where vertical drip or light splashing occurs. Operating temperature is 0...40 °C without derating, 40...50 °C with derating factor — if the room hits 45 °C, expect a current reduction. Altitude derating starts at 1000 m: 1 % per 100 m up to 2000 m, then continues to 4800 m with the same slope, regardless of earthing system (TT, TN, IT). That means at 2000 m the drive loses 10 % of its rated current; at 3000 m, 20 %.
Integration notes
The drive comes with the Spacial SF enclosure, main switch, line choke, and terminal blocks for main supply and motor — no separate enclosure sourcing needed. Communication ports are EtherNet/IP, Modbus serial, and Modbus TCP, so it drops into most control networks without an extra gateway. The graphical operating panel is mounted in the enclosure door; you can remote-mount it if the panel location is awkward. Vibration resistance is 1.5 mm peak-to-peak at 3–20 Hz and 0.6 gn at 10–200 Hz (IEC 60068-2-6), which is standard for floor-mounted industrial gear — not for direct machine mounting. Shock resistance is 4 gn for 11 ms (IEC 60068-2-27). Pollution degree 2 (IEC 61800-5-1) means only non-conductive pollution occurs, so no special coating required for clean indoor air.