Skip to main content
Schneider Electric ATV980C50Q4X1 — AC Drive (VFD) 480V

Schneider ATV980C50Q4X1 ATV980 Regenerative Drive, 500-400kW

MPNATV980C50Q4X1
Active

Schneider Electric Altivar Process ATV900, ATV980 regenerative system, 500 to 400kW, 400V, IP23, CE.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV980C50Q4X1 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV980
Product range / familyAltivar Process ATV900

Input / Supply

ATV980C50Q4X1 — Input / Supply
ParameterValue
Rated supply voltage range380...415 V - 10...6 %
Network number of phases3 phases

Mechanical & Cooling

ATV980C50Q4X1 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP23 conforming to IEC 61800-5-1
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure compact version

Environmental

ATV980C50Q4X1 — Environmental
ParameterValue
Operating ambient temperature-10...0 °C without derating (with option enclosure heating) 0...40 °C without derating 40...50 °C with derating factor
Operating altitude1000...2000 m with current derating 1 % per 100 m 2000...3800 m with current derating 1 % per 100 m for TT earthing system 2000...3800 m with current derating 1 % per 100 m for TN earthing system 2000...3800 m with current derating 1 % per 100 m for IT earthing system 3800...4800 m with current derating 1 % per 100 m for TT earthing system 3800...4800 m with current derating 1 % per 100 m for TN earthing system
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-25...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 3...20 Hz) conforming to IEC 60068-2-6 0.6 gn (f= 10...200 Hz) conforming to IEC 60068-2-6 3M3 conforming to IEC 60721-3-3 1.5 mm peak to peak (f= 3...10 Hz) conforming to IEC 60068-2-6

Approvals

ATV980C50Q4X1 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-2 IEC 61800-3 IEC 61800-5-1 IEC 60204-1

Protection & EMC

ATV980C50Q4X1 — Protection & EMC
ParameterValue
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6

Communication

ATV980C50Q4X1 — Communication
ParameterValue
Communication protocolsModbus serial EtherNet/IP Modbus TCP

Product details

The Schneider Electric ATV980C50Q4X1 is a regenerative variable speed drive from the Altivar Process ATV900 family, specifically the ATV980 regenerative system. It is rated for 500 to 400 kW output at a supply voltage of 380...415 V (-10...6 %), three-phase, 50/60 Hz. This is a compact floor-standing enclosure variant, IP23 rated, with forced convection cooling. It handles both asynchronous and synchronous motors, and is designed to meet IEC 61800-2, -3, -5-1, and IEC 60204-1. The drive includes an enclosure, Spacial SF graphical operating panel mounted in the door, main switch, line choke, dv/dt filter choke, and terminal blocks for main supply and motor — essentially a near-complete drive package for a regenerative application.

The IP23 enclosure is ventilated (forced convection) and suitable for indoor installation where dripping water and limited dust ingress are acceptable. The compact floor-standing format means it occupies a defined footprint on the plant floor, not a panel mount. Total harmonic current distortion (THDI) is less than 5 % at full load, conforming to IEEE 519. That is a strong figure for a regenerative drive — it means the built-in active front end cleans up the line side, reducing the need for external harmonic filters in most installations. Operating temperature range is 0...40 °C without derating, and 40...50 °C with derating. Below 0 °C, an optional enclosure heater is required. Altitude derating starts at 1000 m: 1 % per 100 m up to 2000 m, and continues to 4800 m with the same derating slope, with specific earthing system notes for TT, TN, and IT systems above 2000 m. Communication is via Modbus serial, EtherNet/IP, and Modbus TCP — all standard on board. No option card required for basic network integration.

Lead time and pricing depend on the configuration and quantity — submit an RFQ for a firm commitment.

The drive carries CE marking and complies with IEC 61800-2 (adjustable speed drives), IEC 61800-3 (EMC), IEC 61800-5-1 (safety), and IEC 60204-1 (electrical equipment of machines). Environmental resistance includes chemical pollution class 3C3, dust class 3S3, and humidity class 3K3 per IEC 60721-3-3. EMC immunity is tested to level 3 for electrostatic discharge, radiated RF, conducted RF, and surge (1.2/50 µs - 8/20 µs), and level 4 for fast transients. Vibration resistance is 1.5 mm peak-to-peak at 3...20 Hz and 0.6 gn at 10...200 Hz, conforming to class 3M3.

Frequently asked questions

What is the supply voltage and power range of the ATV980C50Q4X1?

It operates on 380...415 V (-10...6 %) three-phase, 50/60 Hz, and is rated for 500 to 400 kW output.

What enclosure rating does the ATV980C50Q4X1 have?

IP23 conforming to IEC 61800-5-1, with forced convection cooling. It is a compact floor-standing enclosure.

What communication protocols are supported?

Modbus serial, EtherNet/IP, and Modbus TCP are all standard on the drive.

What harmonic performance does the ATV980C50Q4X1 achieve?

Total harmonic current distortion (THDI) is less than 5 % at full load, conforming to IEEE 519.

MPN
ATV980C50Q4X1