Skip to main content
Schneider Electric ATV980C63T4X1

ATV980C63T4X1 Altivar Process ATV980 Regenerative System, 71

MPN ATV980C63T4X1
Active

Variable speed drive, Altivar Process ATV900, ATV980 Regenerative System, 710/560 kW, 480 V, CE, IP23.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV980C63T4X1 specifications
ParameterValue
Main product or component typeVariable speed drive
Voltage1 MOhm 500 V DC for 1 minute to earth
Frequency50...60 Hz +/- 5 %
IP ratingIP23
Temp storage max70 °C
Temp storage min-25 °C
Temp operating max50 °C
Temp operating min-10 °C
Storage temperature-25...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Operating positionVertical +/- 10 degree

Product details

The ATV980C63T4X1 is an Altivar Process ATV980 Regenerative System variable speed drive, rated for 710/560 kW on a 480 V three-phase supply. It is part of the ATV900 series, designed for both asynchronous and synchronous motor control in industrial applications. This drive ships as a compact floor-standing enclosure (IP23) with the enclosure, graphical operating panel, main switch, line choke, dv/dt filter choke, and terminal blocks for main supply and motor included — a near turnkey package for regenerative applications. Rated supply is 480 V +/- 10 % at 50...60 Hz +/- 5 %, three-phase input. Forced convection cooling keeps it running; ambient operating temperature range is 0...40 °C without derating, with derating required from 40...50 °C.

The drive carries CE marking and complies with IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 60204-1 (electrical equipment of machines), and IEC 61800-2 (adjustable speed drives). Pollution degree 2 per IEC 61800-5-1 and overvoltage category III apply. EMC immunity includes electrostatic discharge level 3, radiated RF level 3, fast transient burst level 4, surge level 3, and conducted RF level 3 per the respective IEC 61000-4-x standards. Environmental resistance covers chemical pollution class 3C3, dust class 3S3, and humidity class 3K3 per IEC 60721-3-3.

Integration and deployment

Mount vertically within +/- 10 degrees. Operating altitude from 1000 m up to 4800 m requires current derating of 1 % per 100 m, applicable across TT, TN, and IT earthing systems. Vibration resistance per IEC 60068-2-6: 1.5 mm peak-to-peak at 3...20 Hz, 0.6 gn at 10...200 Hz, class 3M3. Shock resistance: 4 gn for 11 ms per IEC 60068-2-27, class 3M2. Communication ports support Modbus TCP, Modbus serial, and EtherNet/IP — enough for most plant-floor control networks without an external gateway.

MPN