Skip to main content
Schneider Electric ATV9A0C13R4 — AC Drive (VFD) 480V

Schneider ATV9A0C13R4 Altivar Process Drive, 132 kW Normal D

MPNATV9A0C13R4
Active

Schneider Electric Altivar Process ATV900, modular variable speed drive, ATV9A0C13R4, 132 kW at 440 V normal duty, 110 kW heavy duty, IP00, forced convection cooling.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV9A0C13R4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV9A0
Product range / familyAltivar Process ATV900

Power & Output

ATV9A0C13R4 — Power & Output
ParameterValue
Motor power (kW)132.0 kW at 440 V normal duty 110.0 kW at 440 V heavy duty
Continuous output current250.0 A at 2.5 kHz normal duty 211.0 A at 2.5 kHz heavy duty
Max. transient current300.0 A during 60 s (normal duty) 316.5 A during 60 s (heavy duty)
Apparent power163.0 kVA at 440 V normal duty 139.0 kVA at 440 V heavy duty

Input / Supply

ATV9A0C13R4 — Input / Supply
ParameterValue
Rated supply voltage range440 V - 15...10 %
Input line current214.0 A at 440 V (normal duty) 183.0 A at 440 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm at 440 V DC, 1 min, earth

Control & Performance

ATV9A0C13R4 — Control & Performance
ParameterValue
Output frequency range0.1...599 Hz
Asynchronous motor control modesOptimized torque mode Variable torque standard Constant torque standard
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor

Protection & EMC

ATV9A0C13R4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV9A0C13R4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level69 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV9A0C13R4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude0...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation conforming to IEC 44068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 44068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV9A0C13R4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV9A0C13R4 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP

Product details

The Schneider Electric ATV9A0C13R4 is an Altivar Process ATV900 modular variable speed drive sized for 132 kW at 440 V normal duty and 110 kW at 440 V heavy duty, with corresponding line currents of 214 A and 183 A. It handles both synchronous and asynchronous motors, making it a fit for a wide range of industrial motor loads from pumps and fans to conveyors and compressors.

The normal duty rating (132 kW, 214 A) is the continuous rating for standard variable-torque applications like centrifugal pumps and fans. The heavy duty rating (110 kW, 183 A) applies for constant-torque loads such as conveyors or positive-displacement pumps, where the drive must sustain higher torque at low speed. The 163 kVA apparent power at normal duty gives a quick check for transformer sizing. Switching frequency is adjustable from 2.5 to 8 kHz, with derating above the default. For motor cable runs longer than 300 m, the integrated EMC filter is rated to IEC 61800-3 category C3, which covers second-environment industrial installations. The drive also carries STO (Safe Torque Off) rated SIL 3 per IEC 61508, so it can serve in safety-related applications without an external safety relay for the stop function.

Integration and fieldbus options

The drive comes as a modular kit: a 160 kW power module, a control unit, mechanical mounting kits, and a power connection set of fuses. Three option slots (A, B, C) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, EtherCAT, CANopen (daisy chain RJ45, SUB-D 9, or screw terminals), as well as digital/analog I/O and relay extension modules. Slot B also supports encoder interfaces (digital 5/12 V, analog, or resolver). Built-in Ethernet IP/Modbus TCP uses two RJ45 ports on the control block, with auto-negotiation and 10/100 Mbit/s. A separate RJ45 port handles Modbus serial at 4.8 to 38.4 kbit/s on a 2-wire RS-485 physical layer. The Modbus serial supports RTU framing and up to 247 slave addresses.

Frequently asked questions

What are the motor power ratings for the ATV9A0C13R4?

It is rated 132 kW at 440 V for normal duty and 110 kW at 440 V for heavy duty.

What fieldbus options are available for this drive?

Option slots accept Profibus DP V1, PROFINET, DeviceNet, EtherCAT, CANopen, and I/O or relay extension modules. Built-in Ethernet IP/Modbus TCP and Modbus serial are standard.

What is the integrated EMC filter rating?

The filter is integrated and rated for 300 m cable length, conforming to IEC 61800-3 category C3 for industrial environments.

MPN
ATV9A0C13R4