Skip to main content
Schneider Electric ATV9A0C25N6 — AC Drives (VFD)

Schneider ATV9A0C25N6 Altivar Process Drive, 160 kW Normal D

MPNATV9A0C25N6
Active

Schneider Electric Altivar Process ATV900, ATV9A0C25N6, 160 kW normal duty, 225 A line current, integrated C3 EMC filter, STO SIL3, modular variant.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9A0C25N6 — Identification
ParameterValue
Product rangeAltivar Process ATV900
Product / component typeVariable speed drive
ATV9A0C25N6 — Power & Current
ParameterValue
Continuous output current275.0 A at 2.5 kHz normal duty 215.0 A at 2.5 kHz heavy duty
ATV9A0C25N6 — Control & Communication
ParameterValue
Switching frequency2.5 kHz
Synchronous motor control profilePermanent magnet motor Synchronous reluctance motor
Communication protocols / portsEtherNet/IP Modbus serial Modbus TCP
Acceleration / deceleration rampsLinear adjustable separately from 0.01...9999 s
Product destinationSynchronous motors Asynchronous motors
ATV9A0C25N6 — Protection & Environmental
ParameterValue
Protection functionsThermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive
Degree of protection (IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP degree of protectionIP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
ATV9A0C25N6 — Electrical
ParameterValue
Supply frequency50...60 Hz +/- 5 %
Network number of phases3 phases

Product details

The Schneider ATV9A0C25N6 is an Altivar Process ATV900 drive built for 160 kW normal duty on 500 V, pulling 225 A line current. It's a modular variant—comes as a kit with the 200 kW power module, control unit, mechanical mounting, connection set, fuses, and front cover.

Normal duty vs heavy duty

On the 500 V line, this drive delivers 160 kW under normal duty and 132 kW under heavy duty. Line current drops from 225 A to 190 A, apparent power from 195 kVA to 165 kVA. If your load profile is constant torque or high overload, the heavy duty figure governs your sizing. That's the difference between a pump running steady and a crusher that hammers hard.

Cabinet mount, IP00 rated for IP21 or IP54 cabinet integration. Forced convection cooling—leave clearance for airflow. Line side via screw terminal, motor side via M10 bars. Control connections use removable screw terminals, 0.5–1.5 mm². Slot A accepts fieldbus option cards: Profibus DP V1, PROFINET, DeviceNet, EtherCAT, CANopen, or Ethernet IP/Modbus TCP. Slots B and C take I/O or relay extension. Handles synchronous and asynchronous motors, switching frequency 2–4.9 kHz adjustable.

Frequently asked questions

What are the supply specifications for ATV9A0C25N6?

It requires external 24 V DC (19–30 V) for digital inputs, internal 10.5 V DC for reference potentiometer, and internal 24 V DC (21–27 V) for STO and digital inputs. Insulation resistance is 1 MOhm at 500 V DC for 1 minute.

What is the marking on ATV9A0C25N6?

It carries CE marking.

What compliance documentation does ATV9A0C25N6 meet?

It complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1.

MPN