Skip to main content
Schneider Electric ATV9A0C40Q6 — AC Drive (VFD) 600V

Schneider ATV9A0C40Q6 Altivar Process ATV900, 400 kW at 690

MPNATV9A0C40Q6
Active

Schneider Altivar Process ATV900, ATV9A0C40Q6, modular drive 400 kW at 690 V normal duty, 315 kW heavy duty, integrated EMC C3, STO SIL3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9A0C40Q6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9A0
Product / component typeVariable speed drive
ATV9A0C40Q6 — Electrical (input)
ParameterValue
Rated supply voltage690 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current394.0 A 690 V normal duty) 316.0 A 690 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % from 80...100 % of load
ATV9A0C40Q6 — Output / Performance
ParameterValue
Apparent power471.0 kVA at 690 V normal duty 378.0 kVA at 690 V heavy duty
Continuous output current425.0 A at 2.5 kHz normal duty 340.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9A0C40Q6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9A0C40Q6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9A0C40Q6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level70 dB 86/188/EEC
ATV9A0C40Q6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Agency markings / approvalsCE

Product details

Altivar Process ATV900 drive for 690 V heavy-duty applications

The ATV9A0C40Q6 is a modular Altivar Process ATV900 drive from Schneider, rated 400 kW at 690 V for normal duty and 315 kW for heavy duty, with an integrated EMC filter meeting IEC 61800-3 category C3 and safe torque off (STO) to SIL3. It handles synchronous and asynchronous motors, with a switching frequency adjustable from 2 to 4.9 kHz and a line current of 394 A normal duty or 316 A heavy duty at 690 V.

The heavy duty motor power (315 kW at 690 V) defines continuous capability for constant-torque loads like conveyors or extruders; the normal duty rating (400 kW) applies to variable-torque loads such as pumps and fans. Line current at heavy duty (316 A) dictates the upstream breaker and cable cross-section; the prospective line Isc of 50 kA means the drive can be installed on supply networks with high fault current capacity. The integrated EMC filter is rated for 300 m cable at C3 (second environment, industrial), so no external filter is needed for most industrial installations—saves panel space and wiring. STO SIL3 is built in, eliminating the need for a separate safety relay for torque-off functions. It is paired with thermal protection for both motor and drive, plus phase-loss and overcurrent detection.

Supply and control wiring

The drive expects an external 24 V DC supply for digital inputs (19 to 30 V), and generates internal 10.5 V for a reference potentiometer (1 to 10 kOhm) and 24 V for digital inputs and STO logic. Control connections are via removable screw terminals (0.5 to 1.5 mm², AWG 20 to 16), with line and motor connections on M10 bars. Built-in Modbus serial (RS-485, RTU) and Ethernet IP/Modbus TCP (10/100 Mbit/s) provide fieldbus connectivity; option slots accept Profibus DP, PROFINET, EtherCAT, DeviceNet, CANopen, and I/O extension modules.

The drive carries CE marking and complies with IEC 61800-3, 61800-5-1, 61000-3-12, 60721-3, 61508, and 13849-1. The variant is modular, supplied as a kit including control unit, mounting hardware, fuses, and a 200 kW power module.

Frequently asked questions

What are the supply voltage requirements for the control circuitry?

Digital inputs use an external 24 V DC supply (19 to 30 V). Internal supplies provide 10.5 V DC for a reference potentiometer and 24 V DC for digital inputs and STO logic.

What safety function does this drive support?

It includes safe torque off (STO) rated to SIL3, eliminating the need for an external safety relay for torque-off applications.

What EMC compliance does the integrated filter provide?

The integrated EMC filter meets IEC 61800-3 category C3 for second environment (industrial), supporting cable lengths up to 300 m without an external filter.

MPN
ATV9A0C40Q6