Skip to main content
Schneider Electric ATV9A0C40T6 — AC Drive (VFD) 600V

ATV9A0C40T6 Altivar Process Drive 450 hp STO SIL3

MPNATV9A0C40T6
Active

Schneider Electric Altivar Process ATV900, ATV9A0C40T6, modular drive, 450 hp at 600 V normal duty, 394 kVA, STO SIL 3, integrated EMC filter C3, cabinet mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9A0C40T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9A0
Product / component typeVariable speed drive
ATV9A0C40T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current379.0 A 600 V normal duty) 298.0 A 600 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % from 80...100 % of load
ATV9A0C40T6 — Output / Performance
ParameterValue
Apparent power394.0 kVA at 600 V normal duty 310.0 kVA at 600 V heavy duty
Continuous output current425.0 A at 2.5 kHz normal duty 340.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9A0C40T6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9A0C40T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9A0C40T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level70 dB 86/188/EEC
ATV9A0C40T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

The ATV9A0C40T6 is a modular Altivar Process ATV900 drive from Schneider Electric, rated 450 hp at 600 V normal duty (379 A line current) and 350 hp at heavy duty (298 A), with Safe Torque Off SIL 3 as a built-in safety function. It runs both synchronous and asynchronous motors, and the integrated EMC filter meets Category C3 for 300 m cable runs, reducing external filtering needs in industrial installations. Power is supplied at 50/60 Hz, and the drive includes a full set of protective functions: motor thermal, drive thermal, STO, overcurrent, overvoltage, undervoltage, phase loss, and overspeed.

Specifications at a glance

Normal duty delivers 394 kVA apparent power at 600 V; heavy duty delivers 310 kVA. Prospective line short-circuit current rating is 50 kA. Switching frequency is adjustable from 2 to 4.9 kHz with derating; forced convection cooling handles the thermal load inside an IP00 chassis intended for IP21 or IP54 cabinet integration. The drive accepts line-side screw terminals and motor-side M10 bars. Control connections use removable screw terminals, 0.5–1.5 mm². Ambient conditions: pollution degree 2 per IEC 61800-5-1, operating altitude up to 2000 m with derating above 1000 m, shock 4 gn for 11 ms, vibration 1.5 mm at 2–13 Hz and 0.5 gn at 13–200 Hz.

Fieldbus and I/O flexibility

The modular design provides three option slots (A, B, C). Slot A accepts Profibus DP V1, PROFINET, DeviceNet, EtherCAT, CANopen (RJ45, SUB-D 9, or screw terminals). Slots B and C support digital and analog I/O extension modules and a relay output module. Built-in communication includes Modbus serial (RS-485 2-wire, 4.8–38.4 kbps, RTU, 1–247 addresses) and Ethernet IP/Modbus TCP (10/100 Mbps, half/full duplex, auto-negotiation). Digital inputs can be supplied externally at 24 V DC (19–30 V); internal supply for reference potentiometer (1–10 kΩ) is 10.5 V DC ±5%; internal supply for digital inputs and STO is 24 V DC (21–27 V). Insulation resistance is 1 MΩ at 500 V DC for 1 min. Encoder feedback options include a 5/12 V digital encoder interface, analog encoder interface, and resolver interface — all via Slot B.

As part of the Altivar Process ATV900 family, it shares common accessories, software, and documentation with other drives in the series — good for spares continuity and design-in confidence. For firm lead times and pricing specific to your order quantity, submit an RFQ through this listing. The modular slot architecture means option cards (Profibus, PROFINET, EtherCAT, etc.) must be ordered separately for fieldbus integration.

The drive complies with IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental), IEC 61508 & ISO 13849-1 (functional safety), and UL 61800-5-1. Markings include CE; the STO function is rated SIL 3. UL type 1 and type 12 are conformant for cabinet integration. Total harmonic current distortion (THDI) is less than 48% from 80–100% load. Noise level is 70 dB per 86/188/EEC.

Frequently asked questions

What is the supply configuration for digital inputs and STO?

Digital inputs accept an external 24 V DC supply (19–30 V). There is also an internal 24 V DC supply for digital inputs and STO operating at 21–27 V, and a 10.5 V DC ±5% supply for a reference potentiometer (1–10 kΩ).

What markings and certifications does ATV9A0C40T6 carry?

It carries CE marking and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, ISO 13849-1, and UL 61800-5-1. STO is rated SIL 3.

What compliance documentation is available for this drive?

The drive is designed to meet the listed IEC and UL standards. Typical documentation includes a CE declaration of conformity, UL listing information, and functional safety manual for STO. For specific compliance certificates, consult the product documentation or submit an RFQ.

MPN