Skip to main content
Schneider Electric ATV9A0C50R4 — AC Drive (VFD) 480V

Schneider ATV9A0C50R4 Altivar Process Drive, 500 kW at 440 V

MPNATV9A0C50R4
Active

Schneider Electric Altivar Process ATV900, ATV9A0C50R4, 500 kW at 440 V normal duty, 400 kW heavy duty, modular cabinet-mount drive.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV9A0C50R4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV9A0
Product range / familyAltivar Process ATV900

Power & Output

ATV9A0C50R4 — Power & Output
ParameterValue
Motor power (kW)500.0 kW at 440 V normal duty 400.0 kW at 440 V heavy duty
Continuous output current900.0 A at 2.5 kHz normal duty 730.0 A at 2.5 kHz heavy duty
Max. transient current1080.0 A during 60 s (normal duty) 1095.0 A during 60 s (heavy duty)
Apparent power588.0 kVA at 440 V normal duty 475.0 kVA at 440 V heavy duty

Input / Supply

ATV9A0C50R4 — Input / Supply
ParameterValue
Rated supply voltage range440 V - 15...10 %
Input line current771.0 A at 440 V (normal duty) 623.0 A at 440 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm at 440 V DC, 1 min, earth

Control & Performance

ATV9A0C50R4 — Control & Performance
ParameterValue
Output frequency range0.1...599 Hz
Asynchronous motor control modesOptimized torque mode Variable torque standard Constant torque standard
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor

Protection & EMC

ATV9A0C50R4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV9A0C50R4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level71 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV9A0C50R4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude0...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation conforming to IEC 44068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 44068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV9A0C50R4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV9A0C50R4 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP

Product details

The ATV9A0C50R4: Line current at 440 V is 771 A normal duty, 623 A heavy duty. Apparent power is 588 kVA normal duty, 475 kVA heavy duty. The switching frequency is adjustable from 2.5 to 8 kHz with derating. Prospective line short-circuit current is 50 kA. The drive includes STO (Safe Torque Off) rated SIL 3, and provides thermal, overcurrent, short-circuit, and phase-loss protections for both motor and drive. Pollution degree 2 per IEC 61800-5-1.

Integration notes

The drive accepts option cards in slots A, B, and C for Profibus DP V1, PROFINET, DeviceNet, EtherCAT, CANopen, and encoder interfaces. Control connections use removable screw terminals 0.5–1.5 mm². Line-side connection is screw terminal; motor connection uses M10 bars. The control block has two RJ45 for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial. Mounting is cabinet-mount with forced convection cooling. Operating altitude is 0–4800 m with derating above 1000 m. Vibration resistance is 1.5 mm peak-to-peak at 2–13 Hz and 0.5 gn at 13–200 Hz per IEC 60068-2-6.

Frequently asked questions

What are the key power ratings?

Motor power is 500 kW at 440 V normal duty and 400 kW at 440 V heavy duty. Line current is 771 A normal duty and 623 A heavy duty at 440 V.

What safety functions are included?

STO (Safe Torque Off) rated SIL 3 is included, along with thermal, overcurrent, short-circuit, and phase-loss protections for both motor and drive.

What fieldbus options are available?

Option cards for Profibus DP V1, PROFINET, DeviceNet, EtherCAT, and CANopen are available for slot A. Encoder interface modules fit slot B.

MPN