Skip to main content
Schneider Electric ATV9A0C80T6 — AC Drive (VFD) 600V

ATV9A0C80T6 Altivar Process ATV900 Drive, 800 hp

MPNATV9A0C80T6
Active

Schneider Electric Altivar Process ATV900 series, modular drive, 800 hp at 600 V normal duty, 670 A line current, STO SIL3, integrated EMC filter C3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9A0C80T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9A0
Product / component typeVariable speed drive
ATV9A0C80T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current670.0 A 600 V normal duty) 547.0 A 600 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % from 80...100 % of load
ATV9A0C80T6 — Output / Performance
ParameterValue
Apparent power696.0 kVA at 600 V normal duty 568.0 kVA at 600 V heavy duty
Continuous output current830.0 A at 2.5 kHz normal duty 650.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9A0C80T6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9A0C80T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9A0C80T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level73 dB 86/188/EEC
ATV9A0C80T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

800 hp modular drive with STO SIL3

The ATV9A0C80T6: Normal duty line current is 670 A at 600 V; heavy duty drops to 547 A at 600 V – match the duty class to your load profile. Apparent power is 696 kVA normal duty, 568 kVA heavy duty. Prospective short-circuit current rating is 50 kA. Switching frequency is adjustable 2 to 4.9 kHz with a derating factor – plan for reduced current output at higher carrier frequencies. The drive handles both synchronous and asynchronous motors. Integrated EMC filter is category C3 per IEC 61800-3, good for 300 m shielded cable runs without an external filter. Total harmonic current distortion (THDI) stays below 48 % from 80 to 100 % load.

Protection and safety coverage

Additional protections cover the motor and drive: thermal, overcurrent, short-circuit, phase loss, overvoltage, undervoltage, overshoot, overspeed, and control circuit break. The drive complies with IEC 61800-3 (EMC), IEC 61800-5-1 (safety), UL 61800-5-1, and pollution degree 2. Vibration resistance: 1.5 mm peak-peak at 2-13 Hz, 0.5 gn at 13-200 Hz. Shock resistance: 4 gn for 11 ms.

Communication and control interfaces

Built-in Modbus serial (RS-485 2-wire, RTU, 1 to 247 addresses) at 4.8 to 38.4 kbit/s. Slot A accepts optional Profibus DP V1, PROFINET, DeviceNet, EtherCAT, or CANopen (RJ45, SUB-D 9, or screw terminals) communication modules. Ethernet IP/Modbus TCP at 10/100 Mbit/s supports half/full duplex and auto-negotiation. Slot B accepts encoder interface modules (digital 5/12 V, analog, or resolver).

Mounting and cooling

Cabinet mount with IP00 degree of protection; intended for integration into IP21 or IP54 cabinets per both IEC and UL standards. Cooling is forced convection. Ambient relative humidity 5 to 95 % non-condensing.

Actively produced with current lifecycle stage. No end-of-life notification. Quote-to-ship lead time depends on quantity and configuration (control unit, power module, and front cover are included in the kit).

Frequently asked questions

What communication options does this drive support?

Built-in Modbus serial plus slot A modules for Profibus DP V1, PROFINET, DeviceNet, EtherCAT, or CANopen, and native Ethernet IP/Modbus TCP.

What safety function is integrated?

Safe Torque Off (STO) rated SIL 3.

What is the cable length rating of the integrated EMC filter?

Category C3 filter supports 300 m shielded cable runs per IEC 61800-3.

MPN
ATV9A0C80T6