ATV9A0M10R4 - Schneider Electric
MPNATV9A0M10R4
Active
variable speed drive, Altivar Process ATV900, APM, single 440V, 1000kW
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Product type | Variable speed drive |
| Device short name | ATV9A0 |
| Product range / family | Altivar Process ATV900 |
Power & Output
| Parameter | Value |
|---|---|
| Motor power (kW) | 1000.0 kW at 440 V normal duty 800.0 kW at 440 V heavy duty |
| Continuous output current | 1770.0 A at 2.5 kHz normal duty 1420.0 A at 2.5 kHz heavy duty |
| Max. transient current | 2124.0 A during 60 s (normal duty) 2130.0 A during 60 s (heavy duty) |
| Apparent power | 1175 kVA at 440 V normal duty 950.0 kVA at 440 V heavy duty |
Input / Supply
| Parameter | Value |
|---|---|
| Rated supply voltage range | 440 V - 15...10 % |
| Input line current | 1542.0 A at 440 V (normal duty) 1246.0 A at 440 V (heavy duty) |
| Network number of phases | 3 phases |
| Internal/auxiliary supplies | External supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm at 500 V DC, 1 min |
Control & Performance
| Parameter | Value |
|---|---|
| Output frequency range | 0.1...599 Hz |
| Asynchronous motor control modes | Optimized torque mode Variable torque standard Constant torque standard |
| Synchronous motor control modes | Permanent magnet motor Synchronous reluctance motor |
Protection & EMC
| Parameter | Value |
|---|---|
| Integrated EMC filter class | Integrated with 300 m conforming to IEC 61800-3 category C3 |
| Protection functions | Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive |
| EMC immunity tests | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Prospective short-circuit current (Isc) | 50 kA |
Mechanical & Cooling
| Parameter | Value |
|---|---|
| IP degree of protection | IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529 |
| Acoustic noise level | 75 dB conforming to 86/188/EEC |
| Cooling method | Forced convection |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | -10...40 °C without derating 40...50 °C with derating factor |
| Operating altitude | 0...4800 m with current derating above 1000m |
| Relative humidity | 5...95 % without condensation conforming to IEC 60068-2-3 |
| Storage / transport temperature | -40...70 °C |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Vibration resistance | 1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6 |
Approvals
| Parameter | Value |
|---|---|
| Certifications & marking | CE |
| Standards compliance | IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 |
Communication
| Parameter | Value |
|---|---|
| Communication protocols | EtherNet/IP Modbus serial Modbus TCP |
MPN