The ATV9A0M10T6: Line current pulls 833 A in normal duty, 673 A in heavy duty at 600 V. That's the number your wire and bus bar sizing starts from, not the hp rating.
What the duty ratings mean for fit
The 833 A normal-duty figure also sets the SCCR — prospective line Isc is 50 kA. Verify your upstream breaker's interrupting rating coordinates, especially on a 600 V service where fault current runs high.
Mounting and wiring notes for the panel builder
Cabinet mount only. The box ships as a kit: one control unit, one power module (200 kW, forced-convection cooled), front cover, mechanical mounting kits, and a power connection set with fuses. Control wiring lands on removable screw terminals (0.5–1.5 mm² / AWG 20–16). Line and motor connections are M10 bars — plan for lugs that fit a 10 mm bolt. EMC filter is integrated and shields up to 300 m of cable under C3 environment; no external filter needed unless you're chasing stricter emissions limits. Switching frequency is adjustable between 2 and 4.9 kHz. Higher frequency quiets the motor but derates current — factor that into your thermal design if running near full load. IP00 rating inside the cabinet (IP21 or IP54 in an enclosure). Keep the enclosure's pollution degree ≤2 per IEC 61800-5-1.