Skip to main content
Schneider Electric ATV9B0C11T4 — AC Drive (VFD) 480V

Schneider ATV9B0C11T4 Altivar Process ATV900, 150 HP at 480

MPNATV9B0C11T4
Active

Schneider Electric Altivar Process ATV900, modular variable speed drive, ATV9B0C11T4, 150 hp at 480 V normal duty, 148 A line current, STO SIL 3, integrated EMC filter C3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9B0C11T4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV9B0
Product range / familyAltivar Process ATV900
ATV9B0C11T4 — Input / Supply
ParameterValue
Rated supply voltage range480 V
Input line current148.0 A 480 V normal duty) 125.0 A 480 V heavy duty) 122.1 A 480 V regenerative mode normal duty) 100.7 A 480 V regenerative mode heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm at 500 V DC, 1 min, earth
ATV9B0C11T4 — Power & Output
ParameterValue
Continuous output current211.0 A at 2.5 kHz normal duty 173.0 A at 2.5 kHz heavy duty 211.0 A at 2.5 kHz normal duty regenerative mode 173.0 A at 2.5 kHz heavy duty regenerative mode
Max. transient current253.2 A 60 s normal duty) 259.5 A 60 s heavy duty) 253.2 A 60 s regenerative mode normal duty) 259.5 A 60 s regenerative mode heavy duty)
Apparent power123.0 kVA at 480 V normal duty 104.0 kVA at 480 V heavy duty 101.5 kVA at 480 V normal duty regenerative mode 83.7 kVA at 480 V heavy duty regenerative mode
ATV9B0C11T4 — Control & Performance
ParameterValue
Output frequency range0.1...599 Hz
Asynchronous motor control modesOptimized torque mode Variable torque standard Constant torque standard
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor
ATV9B0C11T4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Protection functionsThermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA
ATV9B0C11T4 — Mechanical & Cooling
ParameterValue
Degree of protection (IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP degree of protectionIP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Acoustic noise level70 dB 86/188/EEC
Cooling methodForced convection
ATV9B0C11T4 — Environmental
ParameterValue
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Operating altitude0...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature-40...158 °F (-40...70 °C)
Pollution degree2 IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
ATV9B0C11T4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
ATV9B0C11T4 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP

Product details

Drive rating and supply architecture

The ATV9B0C11T4 is a modular Altivar Process ATV900 drive rated 150 hp at 480 V normal duty, 125 hp heavy duty, with corresponding line currents of 148 A and 125 A at 480 V. In regenerative mode, normal duty is 150 hp at 122.1 A, heavy duty 125 hp at 100.7 A. Apparent power is 123 kVA normal duty, 104 kVA heavy duty at 480 V. Control supply is split: digital inputs take an external 24 V DC (19...30 V), while the STO circuit and digital inputs have a separate internal 24 V DC supply (21...27 V). A 10.5 V DC ±5 % reference is provided for a 1 to 10 kΩ potentiometer.

Safety and compliance

The drive carries CE marking and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, UL 61800-5-1, and others. Integrated EMC filter meets IEC 61800-3 category C3 for cable runs up to 300 m.

Communication and option slots

Three option slots (A, B, C) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), EtherCAT, plus digital/analog I/O and relay extension modules. Slot B also accepts encoder interface modules (digital 5/12 V, analog, resolver). Built-in Ethernet IP/Modbus TCP via 2 RJ45 ports, plus a separate RJ45 for Modbus serial. Modbus serial runs at 4.8 to 38.4 kbit/s, RTU frame, 1...247 addresses.

Frequently asked questions

What are the key ratings for this drive?

Rated 150 hp at 480 V normal duty, 125 hp heavy duty; line current 148 A normal duty, 125 A heavy duty at 480 V. Apparent power 123 kVA normal duty, 104 kVA heavy duty.

What safety functions does it support?

STO (Safe Torque Off) rated SIL 3.

What communication options are available?

Three option slots accept Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, plus I/O and relay extensions. Built-in Ethernet IP/Modbus TCP and Modbus serial.

MPN
ATV9B0C11T4