Schneider Electric ATV9B0C40Q4 — AC Drive (VFD) 480V

Schneider ATV9B0C40Q4 Altivar Process ATV900, 400 kW

MPNATV9B0C40Q4
Active

Schneider Electric Altivar Process ATV900, modular VFD, ATV9B0C40Q4, 400 kW at 400 V normal duty, 315 kW heavy duty, 620 A line current, forced convection cooling.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV9B0C40Q4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV9B0
Product range / familyAltivar Process ATV900

Power & Output

ATV9B0C40Q4 — Power & Output
ParameterValue
Motor power (kW)400.0 kW at 400 V normal duty 315.0 kW at 400 V heavy duty 400.0 kW at 400 V normal duty regenerative mode 315.0 kW at 400 V heavy duty regenerative mode
Continuous output current730.0 A at 2.5 kHz normal duty 590.0 A at 2.5 kHz heavy duty 730.0 A at 2.5 kHz normal duty regenerative mode 590.0 A at 2.5 kHz heavy duty regenerative mode
Max. transient current876.0 A during 60 s (normal duty) 885.0 A during 60 s (heavy duty) 876.0 A during 60 s regenerative mode (normal duty) 885.0 A during 60 s regenerative mode (heavy duty)
Apparent power429.0 kVA at 400 V normal duty 340.0 kVA at 400 V heavy duty 372.7 kVA at 400 V normal duty regenerative mode 291.9 kVA at 400 V heavy duty regenerative mode

Input / Supply

ATV9B0C40Q4 — Input / Supply
ParameterValue
Rated supply voltage range400 V - 15...10 %
Input line current620.0 A at 400 V (normal duty) 491.0 A at 400 V (heavy duty) 537.9 A at 400 V regenerative mode (normal duty) 421.4 A at 400 V regenerative mode (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm at 500 V DC, 1 min, earth

Control & Performance

ATV9B0C40Q4 — Control & Performance
ParameterValue
Output frequency range0.1...599 Hz
Asynchronous motor control modesOptimized torque mode Variable torque standard Constant torque standard
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor

Protection & EMC

ATV9B0C40Q4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6

Mechanical & Cooling

ATV9B0C40Q4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level75 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV9B0C40Q4 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C without derating 40...50 °C with derating factor
Operating altitude0...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV9B0C40Q4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV9B0C40Q4 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP

Product details

The Schneider ATV9B0C40Q4 is an Altivar Process ATV900 modular drive sized for 400 kW at 400 V normal duty or 315 kW heavy duty, pulling 620 A line current in normal duty and 491 A in heavy duty. It handles both asynchronous and synchronous motors, with an integrated EMC filter rated for 300 m cable run to C3 category. Switching frequency is adjustable from 2 to 8 kHz, with derating above 2.5 kHz. The drive includes Safe Torque Off (STO) rated to SIL 3, and thermal, overcurrent, short-circuit, and phase-loss protections on both motor and drive sides.

Slot map and I/O

Three option slots (A, B, C) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT, plus digital/analog I/O or relay extension modules. Slot B also accepts encoder interfaces (digital 5/12 V, analog, or resolver). Built-in Ethernet IP/Modbus TCP on two RJ45 ports, plus one RJ45 for Modbus serial (RS-485, 2-wire, RTU frame, 4.8 to 38.4 kbit/s).

Supply and control power

Digital inputs need an external 24 V DC supply (19...30 V). The drive provides an internal 24 V DC (21...27 V) supply for digital inputs and STO, plus a 10.5 V DC reference for a 1 to 10 kOhm potentiometer. Line supply is three-phase, 50/60 Hz ±5%.

Frequently asked questions

What motors does this drive support?

It is designed for both synchronous and asynchronous motors.

What safety functions are included?

Safe Torque Off (STO) rated to SIL 3 is integrated.

What communication options are available?

Built-in Ethernet IP/Modbus TCP and Modbus serial. Option cards add Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT.

What is the line current rating?

620 A at 400 V normal duty, 491 A at 400 V heavy duty.

MPN