Schneider Electric ATV9B0C40T6 — AC Drive (VFD) 600V

Schneider Electric ATV9B0C40T6 Altivar Process 900 AC Drive

MPNATV9B0C40T6
Active

Schneider Electric Altivar Process ATV900 series, ATV9B0C40T6 modular AC drive, 450 hp at 600 V normal duty, 350 hp heavy duty, forced convection cooling, cabinet mount, IP00 for IP21/IP54 integration.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9B0C40T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9B0
Product / component typeVariable speed drive
ATV9B0C40T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current355.0 A 600 V normal duty) 277.0 A 600 V heavy duty) 228.0 A 600 V regenerative mode normal duty) 162.0 A 600 V regenerative mode heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<5 % full load IEEE 519
ATV9B0C40T6 — Output / Performance
ParameterValue
Apparent power369.0 kVA at 600 V normal duty 288.0 kVA at 600 V heavy duty 237.0 kVA at 600 V normal duty regenerative mode 169.0 kVA at 600 V heavy duty regenerative mode
Continuous output current425.0 A at 2.5 kHz normal duty 340.0 A at 2.5 kHz heavy duty 340.0 A at 2.5 kHz normal duty regenerative mode 275.0 A at 2.5 kHz heavy duty regenerative mode
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9B0C40T6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9B0C40T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9B0C40T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level73 dB 86/188/EEC
ATV9B0C40T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

450 hp at 600 V — normal and heavy duty profiles

The ATV9B0C40T6 is a modular Altivar Process ATV900 drive rated 450 hp at 600 V normal duty and 350 hp at 600 V heavy duty. The heavy-duty line current is 277 A versus 355 A for normal duty — the same drive handles a pump or fan at full nameplate or a crusher/conveyor at the lower derated figure. Apparent power tracks the duty: 369 kVA normal, 288 kVA heavy. The regenerative-mode ratings drop further to 237 kVA normal and 169 kVA heavy, which matters if the application decelerates a high-inertia load and needs to sink regenerated power back to the line.

STO SIL 3 and integrated EMC filter

The drive also integrates an EMC filter rated for 300 m cable runs to IEC 61800-3 category C3, which covers most industrial environments without an external filter. Total harmonic current distortion (THDI) stays below 5 % at full load per IEEE 519 — the active front-end or integrated line reactor handles the harmonics without an add-on filter in most utility grids.

Fieldbus and I/O expansion slots

The control unit carries two RJ45 ports for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial, plus a 2-wire RS-485 physical interface. Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT communication modules; slots A/B/C also accept digital/analog I/O extension and relay output modules. Slot B supports a 5/12 V digital encoder interface, analog encoder interface, or resolver interface. Modbus serial runs at 4.8, 9.6, 19.2, or 38.4 kbit/s with RTU frame and configurable parity; Ethernet ports run at 10/100 Mbit/s. The drive supports 1–247 Modbus addresses.

Frequently asked questions

What compliance documentation does Schneider Electric provide for ATV9B0C40T6?

The drive carries CE marking and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and UL 61800-5-1. Documentation includes the standards declaration and the UL file — request the specific RoHS/REACH declarations at RFQ.