The ATV9B0C56Q4 is a modular Altivar Process ATV900 drive rated for 560 kW at 400 V normal duty and 450 kW heavy duty, with corresponding line currents of 868 A and 697 A. It delivers 601 kVA apparent power under normal duty and 483 kVA under heavy duty. An integrated EMC filter meets IEC 61800-3 category C3 with 300 m of motor cable, and the drive supports STO (safe torque off) SIL 3 as a safety function. It handles synchronous and asynchronous motors, with a switching frequency adjustable from 2 to 8 kHz and a derating factor above 2.5 kHz.
Schneider Electric ATV9B0C56Q4 Altivar Process ATV900, 560 k
MPNATV9B0C56Q4
Active
Schneider Electric Altivar Process ATV900, modular variable speed drive, ATV9B0C56Q4, 560 kW at 400 V normal duty, 868 A line current.
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
Identification
| Parameter | Value |
|---|---|
| Product type | Variable speed drive |
| Device short name | ATV9B0 |
| Product range / family | Altivar Process ATV900 |
Power & Output
| Parameter | Value |
|---|---|
| Motor power (kW) | 560.0 kW at 400 V normal duty 450.0 kW at 400 V heavy duty 560.0 kW at 400 V normal duty regenerative mode 450.0 kW at 400 V heavy duty regenerative mode |
| Continuous output current | 1020.0 A at 2.5 kHz normal duty 830.0 A at 2.5 kHz heavy duty 1020.0 A at 2.5 kHz normal duty regenerative mode 830.0 A at 2.5 kHz heavy duty regenerative mode |
| Max. transient current | 1224.0 A during 60 s (normal duty) 1245.0 A during 60 s (heavy duty) 1224.0 A during 60 s regenerative mode (normal duty) 1245.0 A during 60 s regenerative mode (heavy duty) |
| Apparent power | 601.0 kVA at 400 V normal duty 483.0 kVA at 400 V heavy duty 521.7 kVA at 400 V normal duty regenerative mode 419.2 kVA at 400 V heavy duty regenerative mode |
Input / Supply
| Parameter | Value |
|---|---|
| Rated supply voltage range | 400 V - 15...10 % |
| Input line current | 868.0 A at 400 V (normal duty) 697.0 A at 400 V (heavy duty) 753.0 A at 400 V regenerative mode (normal duty) 605.1 A at 400 V regenerative mode (heavy duty) |
| Network number of phases | 3 phases |
| Internal/auxiliary supplies | External supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm at 500 V DC, 1 min, earth |
Control & Performance
| Parameter | Value |
|---|---|
| Output frequency range | 0.1...599 Hz |
| Asynchronous motor control modes | Optimized torque mode Variable torque standard Constant torque standard |
| Synchronous motor control modes | Permanent magnet motor Synchronous reluctance motor |
Protection & EMC
| Parameter | Value |
|---|---|
| Integrated EMC filter class | Integrated with 300 m conforming to IEC 61800-3 category C3 |
| Protection functions | Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive |
| EMC immunity tests | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Mechanical & Cooling
| Parameter | Value |
|---|---|
| IP degree of protection | IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529 |
| Acoustic noise level | 77 dB conforming to 86/188/EEC |
| Cooling method | Forced convection |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | -5...40 °C without derating 40...50 °C with derating factor |
| Operating altitude | 0...4800 m with current derating above 1000m |
| Relative humidity | 5...95 % without condensation conforming to IEC 60068-2-3 |
| Storage / transport temperature | -40...70 °C |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Vibration resistance | 1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6 |
Approvals
| Parameter | Value |
|---|---|
| Certifications & marking | CE |
| Standards compliance | IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 |
Communication
| Parameter | Value |
|---|---|
| Communication protocols | EtherNet/IP Modbus serial Modbus TCP |
Product details
Frequently asked questions
What are the key power ratings?
Normal duty: 560 kW at 400 V, 868 A line current, 601 kVA. Heavy duty: 450 kW at 400 V, 697 A, 483 kVA. Regenerative mode ratings are also available at the same power levels with slightly lower currents.
What compliance and safety standards does it meet?
IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. Safety function is STO SIL 3.
MPN
ATV9B0C56Q4