Fieldbus and I/O options
The ATV9B0C63Q4: Three option slots (A, B, C) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, plus digital/analog I/O and relay extensions. Slot B also supports encoder interfaces (digital 5/12 V, analog, resolver). Built-in dual-port Ethernet IP/Modbus TCP and a separate Modbus serial port (RS-485, RTU) at 10/100 Mbit/s and up to 38.4 kbit/s respectively.
Power and environmental ratings
Apparent power: 673 kVA normal duty, 537 kVA heavy duty at 400 V. Switching frequency adjustable 2 to 8 kHz with derating. Forced convection cooling. Operates at 50/60 Hz ±5 %, altitude up to 4800 m with derating above 1000 m, ambient humidity 5–95 % non-condensing. Shock resistance 4 gn / 11 ms, vibration 1.5 mm pk-pk at 2–13 Hz.