Skip to main content
Schneider Electric ATV9B0C80T6 — AC Drive (VFD) 600V

ATV9B0C80T6 Altivar Process ATV900, 800 hp at 600 V normal d

MPNATV9B0C80T6
Active

Schneider Electric Altivar Process ATV900, ATV9B0C80T6, 800 hp at 600 V normal duty, 650 hp heavy duty, modular cabinet-mount drive.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9B0C80T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9B0
Product / component typeVariable speed drive
ATV9B0C80T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current628.0 A 600 V normal duty) 513.0 A 600 V heavy duty) 429.0 A 600 V regenerative mode normal duty) 361.0 A 600 V regenerative mode heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<5 % full load IEEE 519
ATV9B0C80T6 — Output / Performance
ParameterValue
Apparent power652.0 kVA at 600 V normal duty 533.0 kVA at 600 V heavy duty 445.0 kVA at 600 V normal duty regenerative mode 375.0 kVA at 600 V heavy duty regenerative mode
Continuous output current830.0 A at 2.5 kHz normal duty 650.0 A at 2.5 kHz heavy duty 650.0 A at 2.5 kHz normal duty regenerative mode 520.0 A at 2.5 kHz heavy duty regenerative mode
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9B0C80T6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9B0C80T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9B0C80T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level77 dB 86/188/EEC
ATV9B0C80T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

The Schneider Electric ATV9B0C80T6 is an Altivar Process ATV900 modular cabinet-mount drive rated for 800 hp at 600 V normal duty and 650 hp at 600 V heavy duty. It handles both synchronous and asynchronous motors, with line current ratings of 628 A (normal duty) and 513 A (heavy duty) at 600 V. The drive includes integrated Safe Torque Off (STO) rated SIL 3, an integrated EMC filter compliant with IEC 61800-3 category C3 (300 m cable), and a switching frequency adjustable from 2 to 4.9 kHz with derating.

The regenerative-mode ratings (650 hp normal duty, 550 hp heavy duty) apply when the motor must brake and return energy to the line — verify your application needs that capability before specifying. Line current at 600 V normal duty is 628 A; heavy duty draws 513 A. These numbers drive the upstream breaker, cable, and buswork sizing. Prospective line short-circuit current rating is 50 kA, so the drive can be installed on a high-fault-capacity distribution panel without additional series protection in most cases. The integrated EMC filter meets category C3 for 300 m of motor cable — sufficient for most industrial installations within a building. For longer cable runs or first-environment (residential) compliance, an external output filter may be required.

Integration notes

This is a modular version — the kit includes the control unit, power module (200 kW), mechanical mounting kits, power connection set, fuses, and three front covers. It mounts in a cabinet (IP00 for IP21 or IP54 cabinet integration). Cooling is forced convection; derate current above 1000 m altitude. Communication options are extensive: three slots (A, B, C) accept modules for Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45 or SUB-D 9 or screw terminals), EtherCAT, plus digital/analog I/O extension and output relay modules. Slot B also accepts encoder interface modules (5/12 V digital, analog, resolver). The base unit includes dual RJ45 Ethernet IP/Modbus TCP ports and one RJ45 Modbus serial port.

Frequently asked questions

What are the key power ratings for this drive?

The drive is rated 800 hp at 600 V normal duty and 650 hp at 600 V heavy duty. Line current is 628 A normal duty, 513 A heavy duty at 600 V.

What safety functions does the ATV9B0C80T6 include?

It includes Safe Torque Off (STO) rated SIL 3, meeting IEC 61508 and IEC 13849-1.

What communication options are available?

The drive has three option slots (A, B, C) supporting Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, plus I/O and relay extension modules. Base ports include dual RJ45 Ethernet IP/Modbus TCP and one RJ45 Modbus serial.

MPN
ATV9B0C80T6