Motor power and duty ratings
The ATV9B0M10Q6: Rated 1000 kW at 690 V in normal duty and 800 kW at 690 V in heavy duty, with corresponding apparent power of 1073 kVA and 859 kVA respectively. Line current at 690 V is 898 A normal duty, 718 A heavy duty. The regenerative mode ratings drop to 621 A and 487 A respectively — factor this in if the application includes a braking resistor or regenerative supply.
Safety and compliance
Integrated EMC filter meets IEC 61800-3 category C3 for 300 m cable runs — suitable for industrial environments with a dedicated transformer or TN-S supply. The filter is built in; no external EMC box needed for most installations. CE marked, with standards compliance to IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. Prospective line Isc is 50 kA — coordinate the upstream breaker accordingly.
Fieldbus and I/O options
Three option card slots (A, B, C) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, plus digital/analog I/O extension and encoder interfaces. Slot A handles the main fieldbus; slot B can take a resolver or encoder feedback card for closed-loop motor control. Built-in dual RJ45 Ethernet IP/Modbus TCP ports plus a separate RJ45 Modbus serial port. The Modbus serial runs at 4.8 to 38.4 kbit/s RTU; Ethernet ports are 10/100 Mbit/s. The drive ships as a Modbus TCP slave by default.