Skip to main content
Schneider Electric ATV9B0M12Q6 — AC Drive (VFD) 600V

Schneider ATV9B0M12Q6 Altivar Process 900, 1200 kW at 690 V

MPNATV9B0M12Q6
Active

Schneider Electric Altivar Process ATV900, modular VFD, 1200 kW at 690 V normal duty, integrated EMC filter C3, STO SIL 3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9B0M12Q6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9B0
Product / component typeVariable speed drive
ATV9B0M12Q6 — Electrical (input)
ParameterValue
Rated supply voltage690 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current1078.0 A 690 V normal duty) 898.0 A 690 V heavy duty) 777.0 A 690 V regenerative mode normal duty) 621.0 A 690 V regenerative mode heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<5 % full load IEEE 519
ATV9B0M12Q6 — Output / Performance
ParameterValue
Apparent power1288.0 kVA at 690 V normal duty 1073.0 kVA at 690 V heavy duty 928.0 kVA at 690 V normal duty regenerative mode 743.0 kVA at 690 V heavy duty regenerative mode
Continuous output current1230.0 A at 2.5 kHz normal duty 1030.0 A at 2.5 kHz heavy duty 1030.0 A at 2.5 kHz normal duty regenerative mode 830.0 A at 2.5 kHz heavy duty regenerative mode
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9B0M12Q6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9B0M12Q6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9B0M12Q6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level79 dB 86/188/EEC
ATV9B0M12Q6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Agency markings / approvalsCE

Product details

The Schneider ATV9B0M12Q6 is a modular Altivar Process ATV900 drive rated for 1200 kW at 690 V normal duty and 1000 kW at 690 V heavy duty. Line current pulls 1078 A at 690 V normal duty, 898 A heavy duty. The integrated EMC filter meets IEC 61800-3 category C3 for 300 m cable runs. Safe torque off (STO) is rated SIL 3.

Supply rails and control wiring

Digital inputs need an external 24 V DC supply (19...30 V). There is an internal 10.5 V DC ±5 % rail for a reference potentiometer (1 to 10 kΩ). The STO and digital input internal supply is a separate 24 V DC rail (21...27 V). Insulation resistance is 1 MΩ at 500 V DC for 1 min.

Option card slots and fieldbus

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT. Slot A/B/C can take digital/analog I/O extension or output relay modules. Slot B handles 5/12 V digital encoder, analog encoder, or resolver interface. Native comms include dual RJ45 Ethernet IP/Modbus TCP and one RJ45 Modbus serial (RS-485 2-wire, RTU, 4.8–38.4 kbit/s, 1–247 addresses).

Frequently asked questions

What are the key motor power ratings?

1200 kW at 690 V normal duty, 1000 kW at 690 V heavy duty, and 1000 kW normal duty / 800 kW heavy duty in regenerative mode.

What safety function does it include?

Safe torque off (STO) rated SIL 3.

What fieldbus options are available via option card?

Slot A supports Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), and EtherCAT.

MPN
ATV9B0M12Q6