Skip to main content
Schneider Electric ATV9B0M12T6 — AC Drive (VFD) 600V

Schneider ATV9B0M12T6 Altivar Process ATV900, 1200 HP

MPNATV9B0M12T6
Active

Schneider Altivar Process ATV900, modular VFD, ATV9B0M12T6, 1200 hp at 600 V normal duty, 1000 hp heavy duty, STO SIL 3, integrated EMC filter C3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9B0M12T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9B0
Product / component typeVariable speed drive
ATV9B0M12T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current937.0 A 600 V normal duty) 785.0 A 600 V heavy duty) 663.0 A 600 V regenerative mode normal duty) 528.0 A 600 V regenerative mode heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<5 % full load IEEE 519
ATV9B0M12T6 — Output / Performance
ParameterValue
Apparent power973.0 kVA at 600 V normal duty 815.0 kVA at 600 V heavy duty 689.0 kVA at 600 V normal duty regenerative mode 548.0 kVA at 600 V heavy duty regenerative mode
Continuous output current1230.0 A at 2.5 kHz normal duty 1030.0 A at 2.5 kHz heavy duty 1030.0 A at 2.5 kHz normal duty regenerative mode 830.0 A at 2.5 kHz heavy duty regenerative mode
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9B0M12T6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9B0M12T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9B0M12T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level79 dB 86/188/EEC
ATV9B0M12T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

The Schneider ATV9B0M12T6 is an active-production Altivar Process ATV900 modular drive sized for a 1200 hp motor at 600 V normal duty, or 1000 hp heavy duty. It ships as a kit: control unit, power module (200 kW), mechanical mounting kit, power connection set with fuses, and front cover. The lifecycle stage is current — no end-of-life notice on record, so this is the line item to spec into a BOM without worrying about a last-time-buy window.

Line current at 600 V normal duty is 937 A; heavy duty pulls 785 A. That puts it squarely in the 1000–1200 hp induction or synchronous motor class. The apparent power numbers — 973 kVA normal, 815 kVA heavy — confirm the transformer and cable sizing a site engineer needs to coordinate. Switching frequency is adjustable 2–4.9 kHz with derating; no one is running this at 4.9 kHz on a 1000 hp load without watching the thermal curve.

Safety and compliance stack

The integrated EMC filter meets IEC 61800-3 category C3 for 300 m of motor cable, which covers most industrial panel-to-motor runs without an external filter. Standards list includes UL 61800-5-1, so the UL Type 1 or Type 12 cabinet integration is straightforward for North American panels.

Fieldbus and I/O flexibility

The drive comes with dual RJ45 ports for Ethernet IP / Modbus TCP (10/100 Mbit/s) and one RJ45 for Modbus serial (RTU at 4.8–38.4 kbit/s). Slot A accepts optional Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT communication modules. Slots A/B/C also take digital/analog I/O or output relay extensions. That means the same drive can slot into a PROFINET line today and migrate to EtherCAT next year by swapping one card.

Frequently asked questions

What are the motor power ratings for the ATV9B0M12T6?

1200 hp at 600 V normal duty, 1000 hp at 600 V heavy duty. In regenerative mode, 1000 hp normal duty and 800 hp heavy duty.

What safety functions does the ATV9B0M12T6 include?

Safe torque off (STO) rated SIL 3, integrated at the drive level.

What communication options are available on this drive?

Built-in dual Ethernet IP/Modbus TCP ports and one Modbus serial port. Slot A accepts optional Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT modules.

Does the drive include an EMC filter?

Yes, an integrated filter rated for 300 m of motor cable, meeting IEC 61800-3 category C3.

MPN