Skip to main content
Schneider Electric BMXAMI0800H — Analog Input Modules

Schneider BMXAMI0800H X80 Analog Input Module 8 Non-Isolated Inputs | aoctrl

MPNBMXAMI0800H
Active

Schneider Electric Modicon X80 analog input module BMXAMI0800H, 8 non-isolated inputs for current/voltage, 16-bit conversion, conformal coated for severe environments.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

BMXAMI0800H key specifications
ParameterValue
Type of filterFirst order digital filtering
Range of productModicon X80
Analogue input typeCurrent +/- 20 mA Current 0...20 mA Current 4...20 mA Voltage +/- 10 V Voltage +/- 5 V Voltage 0...10 V Voltage 0...5 V Voltage 1...5 V
Product or component typeAnalog input module
Isolation voltage1400 V DC between channels and ground 1400 V DC between channels and bus 50 V DC between channels
Power consumption in0.55 W 24 V DC typical 1.01 W 24 V DC maximum 0.32 W 3.3 V DC typical 0.48 W 3.3 V DC maximum
IP degree of protectionIP20
Electrical connection28 ways 1 connector
Shock resistance30 gn
Relative humidity5...95 % at 55 °C without condensation
Operating altitude0...2000 m 2000...5000 m with derating factor
Vibration resistance3 gn

All specifications

BMXAMI0800H additional specifications
ParameterValue
StandardsCSA C22.2 No 61010-2-201 EN/IEC 61131-2 UL 61010-2-201 EN/IEC 61010-2-201
Status LED1 LED (green) RUN 1 LED per channel (green) channel diagnostic 1 LED (red) ERR 1 LED (red) I/O
Input levelHigh level
RecalibrationFactory calibrated
Input impedance250 Ohm
Measurement error0.15 % of full scale +/- 20 mA 25 °C 0.15 % of full scale 0...20 mA 25 °C 0.15 % of full scale 4...20 mA 25 °C 0.075 % of full scale +/- 10 V 25 °C 0.075 % of full scale 0...10 V 25 °C 0.075 % of full scale 0...5 V 25 °C 0.075 % of full scale 1...5 V 25 °C 0.075 % of full scale +/- 5 V 25 °C <= 0.3 % of full scale 4...20 mA - 25...70 °C
Temperature drift30 ppm/°C +/- 10 V 30 ppm/°C +/- 5 V 30 ppm/°C 0...10 V 30 ppm/°C 0...5 V 30 ppm/°C 1...5 V 50 ppm/°C +/- 20 mA 50 ppm/°C 0...20 mA 50 ppm/°C 4...20 mA
Digital value format+/- 32767 in user scale +/- 10000 by default
Fast read cycle time1 ms + 1 ms x number of channels used
Protective treatmentConformal coating Humiseal 1A33 TC
Analogue input number8
Measurement resolution0.36 mV +/- 10 V 0.36 mV 0...10 V 0.36 mV 0...5 V 0.36 mV 1...5 V 0.36 mV +/- 5 V 1.4 µA +/- 20 mA 1.4 µA 0...20 mA 1.4 µA 4...20 mA
Nominal read cycle time9 ms for 8 channels
Maximum conversion value+/- 11.4 V +/- 10 V +/- 11.4 V 0...10 V +/- 11.4 V 0...5 V +/- 11.4 V 1...5 V 0...30 mA +/- 20 mA 0...30 mA 0...20 mA 0...30 mA 4...20 mA 0...30 mA +/- 5 V
Analog (digital conversion)16 bits
Analogue input resolution15 bits + sign
Isolation between channelsNon isolated
Environmental characteristicCorrosion resistance Dust resistant
Permitted overload on inputs+/- 30 mA 0...20 mA +/- 30 mA 4...20 mA +/- 30 V +/- 10 V +/- 30 V +/- 5 V +/- 30 V 0...10 V +/- 30 V 0...5 V +/- 30 V 1...5 V +/- 30 mA +/- 20 mA
Product specific applicationFor severe environments
Minimum crosstalk attenuation80 dB
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
Precision of internal conversion resistor0.1 % - 15 ppm/°C

Product details

Built for harsh environments

The BMXAMI0800H is an 8-channel analog input module in the Modicon X80 family, explicitly designed for severe environments. That means a panel OEM can place this module in a non-conditioned cabinet or near washdown zones without the usual derating or extra protective covers.

Precision and input flexibility

8 inputs accept voltage and current ranges with 16-bit conversion and 15 bits + sign resolution. Accuracy is 0.15 % FS on current and 0.075 % FS on voltage at 25 °C, with drift of 50 ppm/°C on current and 30 ppm/°C on voltage.

Cycle time and scan performance

Nominal read cycle time is 9 ms for 8 channels. Fast read cycle time is 1 ms + 1 ms per active channel.

Isolation and wiring

Channel-to-channel isolation is non-isolated – so if you need true per-channel galvanic separation for mixing signal types, this isn't the card. But channel-to-bus and channel-to-ground isolation is 1400 V DC, which handles common-mode voltages from external faults. Input impedance is 250 Ω on current ranges, so loop-powered transmitters see a standard burden. The 28-way connector handles all field wiring in one plug.

Frequently asked questions

What is the accuracy of the BMXAMI0800H?

Accuracy is 0.15 % of full scale on current ranges and 0.075 % on voltage ranges at 25 °C. Temperature drift is 50 ppm/°C on current, 30 ppm/°C on voltage.

Is the module suitable for severe environments?

Yes, it has conformal coating, operates from -25 °C to 70 °C, and is rated for corrosion and dust resistance. It is specifically listed for severe environments.

What isolation does the BMXAMI0800H provide?

Channel-to-channel is non-isolated. Channel-to-ground and channel-to-bus are isolated at 1400 V DC. Between channels the isolation is 50 V DC.

MPN