Skip to main content
Schneider Electric BMXART0814H

BMXART0814H Modicon X80 Analog Input Module, 8 TC/RTD, Isola

MPNBMXART0814H
Active

Schneider Electric BMXART0814H, Modicon X80, Analog input module, 8 TC/RTD isolated inputs, 16-bit sigma-delta.

$673.10 – $1,543.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

BMXART0814H key specifications
ParameterValue
Detection typeOpen circuit Cu 10 Open circuit Ni 100 Open circuit Ni 1000 Open circuit Pt 100 Open circuit Pt 1000 Open circuit thermocouple B Open circuit thermocouple E Open circuit thermocouple J Open circuit thermocouple K Open circuit thermocouple L Open circuit thermocouple N Open circuit thermocouple R Open circuit thermocouple S Open circuit thermocouple T Open circuit thermocouple U
Type of filterFirst order digital filtering
Range of productModicon X80
Analogue input typeVoltage +/- 1.28 V Voltage +/- 160 mV Voltage +/- 320 mV Voltage +/- 40 mV Voltage +/- 640 mV Voltage +/- 80 mV Resistor 400 Ohm 2 wires Resistor 400 Ohm 3 wires Resistor 400 Ohm 4 wires Resistor 4000 Ohm 2 wires Resistor 4000 Ohm 3 wires Resistor 4000 Ohm 4 wires Temperature probe -100...+260 °C Cu 10 Temperature probe -100...+450 °C Pt 100 conforming to UL/JIS Temperature probe -100...+450 °C Pt 1000 conforming to UL/JIS Temperature probe -200...+850 °C Pt 100 conforming to IEC Temperature probe -200...+850 °C Pt 1000 conforming to IEC Temperature probe -60...+180 °C Ni 100 Temperature probe -60...+180 °C Ni 1000 Thermocouple +130...+1820 °C thermocouple B Thermocouple +270...+1300 °C thermocouple N Thermocouple -200...+600 °C thermocouple U Thermocouple -200...+760 °C thermocouple J Thermocouple -200...+900 °C thermocouple L Thermocouple -270...+1000 °C thermocouple E Thermocouple -270...+1370 °C thermocouple K Thermocouple -270...+400 °C thermocouple T Thermocouple -50...+1769 °C thermocouple R Thermocouple -50...+1769 °C thermocouple S
Product or component typeAnalog input module
Current consumption150 mA at 3.3 V DC 50 mA at 24 V DC
IP degree of protectionIP20
Electrical connection40 ways 2 connectors
Shock resistance30 gn
Relative humidity5...95 % at 55 °C without condensation
Operating altitude0...2000 m 2000...5000 m with derating factor
Vibration resistance3 gn

All specifications

BMXART0814H additional specifications
ParameterValue
MTBF reliability900000 H
StandardsIEC 61131-2 IEC 61000-6-4 IEC 61000-6-2 EN 61010-2-201
Directives2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility
Status LED1 LED (green) RUN 1 LED per channel (green) channel diagnostic 1 LED (red) ERR 1 LED (red) I/O
Input levelLow level
RecalibrationInternal
Measurement error+/- 0.7 °C Ni 1000 25 °C +/- 2.1 °C Ni 100 25 °C +/- 2.1 °C Pt 100 25 °C +/- 2.1 °C Pt 1000 25 °C +/- 2.7 °C thermocouple U 25 °C +/- 2.8 °C thermocouple J 25 °C +/- 3 °C thermocouple L 25 °C +/- 3.2 °C thermocouple R 25 °C +/- 3.2 °C thermocouple S 25 °C +/- 3.5 °C thermocouple B 25 °C +/- 3.7 °C thermocouple E 25 °C +/- 3.7 °C thermocouple K 25 °C +/- 3.7 °C thermocouple N 25 °C +/- 3.7 °C thermocouple T 25 °C +/- 4 °C Cu 10 25 °C 0.05 % of full scale +/- 1.28 V 25 °C 0.05 % of full scale +/- 160 mV 25 °C 0.05 % of full scale +/- 320 mV 25 °C 0.05 % of full scale +/- 40 mV 25 °C 0.05 % of full scale +/- 640 mV 25 °C 0.05 % of full scale +/- 80 mV 25 °C 0.12 % of full scale 400 Ohm 25 °C 0.12 % of full scale 4000 Ohm 25 °C +/- 1.5 °C Ni 1000 - 25...70 °C +/- 3.5 °C Ni 100 - 25...70 °C +/- 3.5 °C Pt 100 - 25...70 °C +/- 3.5 °C Pt 1000 - 25...70 °C +/- 4.5 °C Cu 10 - 25...70 °C +/- 5.5 °C thermocouple J - 25...70 °C +/- 5.5 °C thermocouple L - 25...70 °C +/- 5.5 °C thermocouple R - 25...70 °C +/- 5.5 °C thermocouple S - 25...70 °C +/- 5.5 °C thermocouple U - 25...70 °C +/- 6 °C thermocouple B - 25...70 °C +/- 6 °C thermocouple E - 25...70 °C +/- 6 °C thermocouple K - 25...70 °C +/- 6 °C thermocouple N - 25...70 °C +/- 6 °C thermocouple T - 25...70 °C <= 0.3 % of full scale 4000 Ohm - 25...70 °C
Temperature drift25 ppm/°C 400 Ohm 25 ppm/°C 4000 Ohm 25 ppm/°C Ni 1000 25 ppm/°C thermocouple B 25 ppm/°C thermocouple E 25 ppm/°C thermocouple J 25 ppm/°C thermocouple K 25 ppm/°C thermocouple L 25 ppm/°C thermocouple N 25 ppm/°C thermocouple R 25 ppm/°C thermocouple S 25 ppm/°C thermocouple T 25 ppm/°C thermocouple U 30 ppm/°C +/- 1.28 V 30 ppm/°C +/- 160 mV 30 ppm/°C +/- 320 mV 30 ppm/°C +/- 40 mV 30 ppm/°C +/- 640 mV 30 ppm/°C +/- 80 mV 30 ppm/°C Cu 10 30 ppm/°C Ni 100 30 ppm/°C Pt 100 30 ppm/°C Pt 1000
Protective treatmentConformal coating
Analogue input number8
Common mode rejection120 dB 50/60 Hz
Measurement resolution0.1 °C Cu 10 0.1 °C Ni 100 0.1 °C Ni 1000 0.1 °C Pt 100 0.1 °C Pt 1000 0.1 °C thermocouple B 0.1 °C thermocouple E 0.1 °C thermocouple J 0.1 °C thermocouple K 0.1 °C thermocouple L 0.1 °C thermocouple N 0.1 °C thermocouple R 0.1 °C thermocouple S 0.1 °C thermocouple T 0.1 °C thermocouple U 1280/2exp14 mV +/- 1.28 V 160/2exp14 mV +/- 160 mV 320/2exp14 mV +/- 320 mV 40/2exp14 mV +/- 40 mV 12.5 mOhm 400 Ohm 125 mOhm 4000 Ohm 640/2exp14 mV +/- 640 mV 80/2exp14 mV +/- 80 mV
Nominal read cycle time400 ms with temperature probe 200 ms with thermocouple
Maximum conversion value+/- 100 % 400 Ohm +/- 100 % 4000 Ohm +/- 102.5 % +/- 1.28 V +/- 102.5 % +/- 160 mV +/- 102.5 % +/- 320 mV +/- 102.5 % +/- 40 mV +/- 102.5 % +/- 640 mV +/- 102.5 % +/- 80 mV
Analog (digital conversion)Sigma delta 16 bits
Analogue input resolution15 bits + sign
Maximum wiring resistance20 Ohm 2 wires Cu 10 20 Ohm 2 wires Ni 100 20 Ohm 2 wires Pt 100 20 Ohm 3 wires Cu 10 20 Ohm 3 wires Ni 100 20 Ohm 3 wires Pt 100 200 Ohm 2 wires Ni 1000 200 Ohm 2 wires Pt 1000 200 Ohm 3 wires Ni 1000 200 Ohm 3 wires Pt 1000 50 Ohm 4 wires Cu 10 50 Ohm 4 wires Ni 100 50 Ohm 4 wires Pt 100 500 Ohm 4 wires Ni 1000 500 Ohm 4 wires Pt 1000
Cold junction compensationExternal by Pt100 probe
Isolation between channelsIsolated
Differential mode rejection60 dB 50/60 Hz
Environmental characteristicGas resistant class Gx Gas resistant class 3C4 Dust resistant class 3S4 Sand resistant class 3S4 Salt resistant level 2 Mold growth resistant class 3B2 Fungal spore resistant class 3B2 Hazardous location class I division 2
Permitted overload on inputs+/- 7.5 V +/- 1.28 V +/- 7.5 V +/- 160 mV +/- 7.5 V +/- 320 mV +/- 7.5 V +/- 40 mV +/- 7.5 V +/- 640 mV +/- 7.5 V +/- 80 mV
Product specific applicationFor severe environments
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C

Product details

The BMXART0814H is an 8-channel analog input module from the Modicon X80 range, designed for thermocouple and RTD sensors with full channel-to-channel isolation and a 16-bit sigma-delta converter. It accepts voltage signals from ±40 mV to ±1.28 V, resistive sensors up to 4000 Ω, and a wide range of thermocouple types (B, E, J, K, L, N, R, S, T, U) as well as Pt100, Pt1000, Ni100, Ni1000, and Cu10 RTDs. Read cycle time runs 400 ms for RTD probes and 200 ms for thermocouples, with a resolution of 0.1 °C across all temperature probes.

Mounting and environmental resilience

Conformal coated, rated for severe environments and gas (Gx/3C4), dust/sand (3S4), salt (level 2), mold/fungal (3B2) resistance, and Class I Division 2 hazardous locations. Operates -25 to 70 °C, 30 gn shock, 3 gn vibration, IP20. Electrical connection is via two 40-way connectors. Channel-to-channel isolation means a fault on one input won't pull down the others—critical for mixed-sensor panels. Internal cold-junction compensation uses an external Pt100 probe. Common-mode rejection is 120 dB, differential-mode rejection 60 dB at 50/60 Hz.

Frequently asked questions

What standards does the BMXART0814H comply with?

It conforms to IEC 61131-2, IEC 61000-6-4, IEC 61000-6-2, and EN 61010-2-201.

What EU directives does the BMXART0814H meet?

It complies with the Low Voltage Directive 2014/35/EU and the EMC Directive 2014/30/EU.

MPN
BMXART0814H