Motor Circuit Protector, TeSys BV4, standard fault, 115A, 600Y/347 VAC, 600 to 1150 instantaneous trip, up to 100kA SCCR

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

BV4T115D — Identification
ParameterValue
Product typeMotor Circuit Protector
Product range / familyTeSys
Product name / familyTeSys BV4
BV4T115D — Ratings
ParameterValue
Rated operational voltage (Ue)600Y/347 V AC 50/60 Hz
BV4T115D — Contacts & Poles
ParameterValue
Number of poles3P
BV4T115D — Performance
ParameterValue
Mechanical durability (cycles)40000 cycles
BV4T115D — Mechanical
ParameterValue
Electrical connection / terminals2 EverLink BTR screw connectors 0.002...0.1 in² (1.5...70 mm²) AWG 14...AWG 2/0), solid copper 2 EverLink BTR screw connectors 0.002...0.08 in² (1.5...50 mm²) AWG 6...AWG 1/0), flexible copper
Terminal tightening torque44.3 lbf.in (5 N.m) 0.02 in² (10 mm²) (AWG 8) 79.7 lbf.in (9 N.m) 0.02 in² (16 mm²) (AWG 6)
IP degree of protectionIP40 front face IEC 60529
Width3.2 in (81 mm)
Height6.4 in (162 mm)
Depth4.6 in (116 mm)
BV4T115D — Environmental
ParameterValue
Operating ambient temperature-13...158 °F (-25...70 °C)
Storage ambient temperature-58...185 °F (-50...85 °C)
Operating altitude6561.68 ft (2000 m) without derating > 2000...5000 m with derating
BV4T115D — Approvals
ParameterValue
StandardsCSA C22.2 No 5 UL 489
BV4T115D — Specifications
ParameterValue
Control typeToggle
MPN
BV4T115D