Skip to main content
Schneider Electric C063N45EFM — Miniature Circuit Breakers (MCB)

Schneider Electric C063N45EFM ComPacT NS 630A 4P MCCB, 50kA

MPNC063N45EFM
Active

Schneider Electric ComPacT NS new generation, C063N45EFM, 630 A, 4-pole, fixed-mounted MCCB with MicroLogic 5.0 E electronic trip unit, 50 kA Icu at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063N45EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063N45EFM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063N45EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063N45EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063N45EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063N45EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063N45EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The Schneider Electric C063N45EFM is a ComPacT NS new generation 4-pole molded case circuit breaker rated 630 A at 50 °C, with a MicroLogic 5.0 E electronic trip unit. It carries a 50 kA Icu breaking capacity at 415 V AC (50/60 Hz) per EN/IEC 60947-2, making it a distribution-grade device for main or feeder protection in commercial and industrial switchboards.

The MicroLogic 5.0 E trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection curves, plus integrated energy metering. The electronic design includes a 20-minute thermal memory that retains the thermal model after a trip, so re-energizing a hot breaker doesn't reset the protection state — relevant for motor or transformer feeders where repeated inrush can mask an overload condition.

Rated Icu is 85 kA at 240 V AC, 50 kA at 415 V and 440 V AC, 40 kA at 500/525 V AC, and 30 kA at 690 V AC. The 50 kA at 415 V (code N) is the typical specification for 400 V class distribution — the breaker coordinates cleanly with downstream 50 kA-rated switchgear without requiring a current-limiting upstream device at that voltage.

Mounting and enclosure fit

Fixed-mounted on a backplate with front connections both top and bottom. Dimensions are 327 mm high, 280 mm wide, 147 mm deep — the 70 mm pole pitch matches standard busbar centers for 4-pole distribution blocks. IP40 enclosure protection and IK07 impact resistance suit indoor panel installation; the 10,000-cycle mechanical durability and 2,000-cycle electrical durability at full rated current (690 V In) define the maintenance interval.

Frequently asked questions

What is the breaking capacity of C063N45EFM at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What trip unit does the C063N45EFM use?

MicroLogic 5.0 E electronic trip unit with L, S, and I protection and integrated energy metering.

What are the mounting dimensions of C063N45EFM?

327 mm high, 280 mm wide, 147 mm deep. Fixed backplate mount with 70 mm pole pitch.

Where can I buy C063N45EFM and get current pricing?