Skip to main content
Schneider Electric C063N42AFM — Miniature Circuit Breakers (MCB)

Schneider Electric C063N42AFM ComPacT NS 630A 4P MCCB, 50 kA

MPNC063N42AFM
Obsolete

Schneider Electric ComPacT NS new generation, C063N42AFM, 630 A, 4P, MicroLogic 2.0 A electronic trip unit, 50 kA at 415 V AC, fixed mount, front connection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063N42AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063N42AFM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063N42AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063N42AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063N42AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063N42AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063N42AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C063N42AFM is a ComPacT NS new generation moulded-case circuit breaker rated 630 A at 50 °C, with a MicroLogic 2.0 A electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection. It is a 4-pole, fixed-mount unit with front connections top and bottom, sized for backplate mounting in a distribution panel. The 630 A frame covers high-current feeders or main incomers in commercial and industrial switchboards. Breaking capacity is the headline selector: 85 kA Icu at 220/240 V AC, 50 kA at 380/415 V AC, and 50 kA at 440 V AC per IEC 60947-2. That N-breaking-capacity code (50 kA at 415 V) means it handles most utility-fault levels without cascading upstream. The MicroLogic 2.0 A is an electronic trip unit, not thermal-magnetic, so it holds its calibration tighter across ambient temperature swings. Thermal memory is 20 minutes — after a trip, the breaker remembers the heat profile for that window, preventing immediate reclose on a still-hot circuit. Four red LEDs signal fault type; one yellow LED flags overload pre-alarm.

Fixed-mount on a backplate, 70 mm connection pitch between poles. Dimensions: 327 mm high, 280 mm wide, 147 mm deep. IP40 enclosure protection (finger-safe), IK07 impact resistance. Overvoltage category III, so it's rated for fixed-installation distribution boards downstream of the service entrance. Neutral is on the left (4-pole, switched neutral). Front connections both sides simplify busbar or cable landing in a standard switchboard layout. Electrical durability: 2000 cycles at 690 V In, 5000 cycles at 440 V In. Mechanical durability: 10,000 cycles. For high-cycle applications like welding or furnace switching, that's a factor to check against your expected operations.

Operating altitude: 0–2000 m without derating, 2000–5000 m with derating. Relative humidity 0–95 %. Power losses at rated current: 10 W — relevant for thermal management inside a sealed enclosure.

Frequently asked questions

Where can I buy C063N42AFM and how do I get a price?

The C063N42AFM is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is the breaking capacity of C063N42AFM at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The breaking capacity code is N (50 kA at 415 V AC).

What trip unit does C063N42AFM use?

MicroLogic 2.0 A electronic trip unit with L (long-time overload) and I (instantaneous short-circuit) protection. It includes a 20-minute thermal memory and LED fault indication.

MPN
C063N42AFM