Skip to main content
Schneider Electric C063N460FM

Schneider Electric C063N460FM ComPacT NS 630A 4P MCCB, Micro

MPN C063N460FM
Obsolete

Schneider Electric ComPacT NS new generation, C063N460FM, 4P MCCB, 630 A, MicroLogic 6.0 trip unit, 50 kA Icu at 415 V AC, IP40, fixed mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C063N460FM key specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Utilization categoryCategory B
IP ratingIP40
Terminal pitch70 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C063N460FM additional specifications
ParameterValue
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degree3 conforming to IEC 60947
Depth147 mm
Width280 mm
Height327 mm
Electrical life cycles2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C063N460FM is a ComPacT NS630b...1600 new generation molded-case circuit breaker, four-pole, rated 630 A at 50 °C with a MicroLogic 6.0 electronic trip unit. It delivers 50 kA Icu at 415 V AC (50/60 Hz) per IEC 60947-2, making it a solid choice for distribution panels where you need selectivity and short-circuit coordination downstream of a transformer.

The 630 A frame gives you headroom on a 400–600 A feeder — you're not running it at the limit, so thermal memory (20 min reset) won't nuisance-trip on a warm motor start. The MicroLogic 6.0 covers L, S, I, and G protection curves; the G (ground-fault) function is built into the trip unit, so you don't need an external relay for earth-leakage on solidly-grounded systems. Category B utilisation means the breaker is designed for discrimination (selectivity) with downstream devices — the short-time delay (S) lets you coordinate with feeder breakers upstream. Breaking capacity steps: 85 kA at 240 V, 50 kA at 415 V, 40 kA at 525 V, 30 kA at 690 V. If your service entrance is 480 V (nominal 480/277 V), you're looking at roughly 50 kA Icu — enough for most industrial distribution transformers up to 1500 kVA. The IP40 front face and IK07 impact resistance handle accidental tool drops in a panel; not washdown-rated, so keep it inside the enclosure. Mechanical durability is 10,000 cycles; electrical durability ranges from 2,000 cycles at full load (690 V In) to 6,000 cycles at half load (440 V In/2). For a main breaker that cycles only a few times a year, that's effectively life-of-installation. The fixed mount and front-connect terminals (upside and downside) simplify bus-bar layout — 70 mm connection pitch matches standard Schneider panelboard patterns.

MPN
C063N460FM