The C063N42EFM: Breaking capacity hits 85 kA Icu at 240 V AC, 50 kA at 415 V, and still holds 30 kA at 690 V — all per IEC 60947-2. The MicroLogic 2.0 E gives you L (long-time overload) and I (instantaneous short-circuit) protection curves, plus an energy meter built into the trip unit. The LCD display shows metering data locally — useful for spot-checking load without opening the panel door.
Fixed-mount on a backplate, 70 mm connection pitch. Front connections top and bottom — standard for panel build, no special bus adaptors needed. IP40 enclosure, IK07 impact rating; fine for indoor distribution boards, not for washdown zones. Dimensions are 327 H x 280 W x 147 D mm. Neutral on the left. The 4-pole format covers 3-phase plus neutral, common for TN or TT systems where you need to break all poles. Overvoltage category III covers fixed-installation distribution.
Mechanical durability is 10,000 cycles; electrical durability varies from 2,000 cycles at 690 V full load to 6,000 cycles at 440 V half load.