Skip to main content
Schneider Electric C063N450FM — Miniature Circuit Breakers (MCB)

Schneider Electric C063N450FM ComPacT NS Circuit Breaker, 63

MPNC063N450FM
Active

Schneider Electric ComPacT NS new generation, C063N450FM, 4-pole circuit breaker, 630 A at 50 °C, 85 kA Icu at 240 V AC, MicroLogic 5.0 electronic trip unit, fixed mount, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063N450FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063N450FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063N450FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063N450FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063N450FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063N450FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063N450FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The Schneider Electric C063N450FM is a ComPacT NS new generation 4-pole circuit breaker with a MicroLogic 5.0 electronic trip unit rated 630 A at 50 °C. It's built for distribution duty in fixed-mount backplate installations, so it bolts into a switchboard or panel — not a snap-on DIN rail job. With a 147 mm depth and 280 mm width, it takes up a defined footprint you can lay out in the cabinet layout. The breaking capacity is 85 kA Icu at 220/240 V AC and 50 kA Icu at 380/415 V AC, both per IEC 60947-2.

If your panel runs hotter than that, you'll need to derate per the manufacturer's curve — that's standard for any molded-case breaker. The MicroLogic 5.0 gives you LSI protection: long-time (L) for overload, short-time (S) for low-level short circuits, and instantaneous (I) for high faults. That's a step up from a thermal-magnetic unit because you can tune the S pickup and delay for selective coordination downstream. Electrical durability is 2,000 cycles at 690 V at full rated current, and 6,000 cycles at 440 V at half current. That's not a daily-switching contactor — it's a distribution breaker meant to stay closed and only open on fault or for isolation. Mechanical durability is 10,000 cycles, which covers years of infrequent manual operation.

Fixed mount on a backplate, with front connections both upside and downside. Connection pitch is 70 mm, which matches standard busbar or cable lug spacing for this frame size. IK07 impact rating handles a 2 J hammer blow, so it survives a dropped wrench during commissioning.

Frequently asked questions

What is the closest alternative to C063N450FM in the ComPacT family?

Within the same ComPacT NS new generation range, the closest sibling would be a unit with the same frame and trip rating but a different breaking capacity code — for instance, an N-break (50 kA at 415 V) vs. the S-break (85 kA at 415 V). The C063N450FM carries the N code (50 kA at 415 V), so if you need more fault-interrupting margin at 415 V, you'd step up to the S-break variant. Both share the same footprint and MicroLogic 5.0 trip unit.

What compliance documentation does Schneider provide for C063N450FM?

The breaker is designed to EN/IEC 60947-2 standards. Schneider typically provides a Declaration of Conformity covering CE and UKCA, plus UL/CSA recognition for the North American market. RoHS and REACH compliance declarations are available on request through the documentation portal.

MPN