Skip to main content
Schneider Electric C063S3NAFM — Miniature Circuit Breakers (MCB)

C063S3NAFM ComPacT NS630b NA Switch Disconnector, 630A 3P

MPNC063S3NAFM
Active

Schneider Electric ComPacT NS new generation, switch disconnector C063S3NAFM, 3P, fixed, manually operated, 630 A AC-23A, IP40, IEC 60947-3.

$1,596.40Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063S3NAFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product/component typeSwitch disconnector
Device applicationDistribution
C063S3NAFM — Ratings
ParameterValue
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-3
Network type (AC/DC)AC
Network frequency50/60 Hz
C063S3NAFM — Protection
ParameterValue
Suitability for isolationYes conforming to IEC 60947-3
Electrical durability (cycles)2000 cycles 440 V AC 50/60 Hz conforming to IEC 60947-3
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-3
C063S3NAFM — Mechanical
ParameterValue
Mounting modeFixed
Control typeManually operated
Contact position indicatorYes
Width327 mm
Height210 mm
Depth147 mm
C063S3NAFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-3
C063S3NAFM — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The rated short-time withstand current (Icw) of 25 kA for 0.5 s tells you this disconnector coordinates with downstream protective devices that clear fast faults within that window, and the 52 kA making capacity (Icm) at 690 V means it can close onto a bolted fault without welding contacts. Isolation suitability per IEC 60947-3 is confirmed, with an 8 kV impulse withstand voltage (Uimp) and pollution degree 3 — so it's certified for safe visible isolation of a circuit, not just load breaking.

Fixed-mount, front connection both sides, 70 mm pole pitch — that's the standard ComPacT NS footprint, so it drops into an existing cutout or busbar system without re-drilling. The IP40 enclosure keeps dust and stray tools out of the switching chamber; IK07 means it survives a 2 J impact during installation. Ambient range of -25 to 70 °C operating and -50 to 85 °C storage covers unheated warehouses and outdoor cabinets in most climates.

Frequently asked questions

Where can I buy C063S3NAFM and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for this exact order code.

What is C063S3NAFM's rated operational current at 690 V?

630 A continuous in AC-23A duty across the full voltage range from 220 V to 690 V AC, 50/60 Hz — no derating at the top end for this utilization category.

What compliance documentation does this brand provide for C063S3NAFM?

The switch disconnector is certified to IEC 60947-3, with pollution degree 3, IP40 per IEC 60529, and IK07 per EN 50102. No RoHS or REACH statements are in the current record, but standard Schneider Electric compliance documentation applies for this active catalog number.

MPN
C063S3NAFM