Skip to main content
Schneider Electric C063H32AFM — Miniature Circuit Breakers (MCB)

Schneider Electric C063H32AFM ComPacT NS 630A 3P MCCB, 70kA

MPNC063H32AFM
Active

Schneider Electric ComPacT NS new generation, manually operated MCCB, 630 A, 3P, MicroLogic 2.0 A electronic trip unit, 70 kA Icu at 415 V AC, fixed mount, front connections.

$2,439.49Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063H32AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063H32AFM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063H32AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063H32AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063H32AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063H32AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063H32AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C063H32AFM is a ComPacT NS new generation moulded-case circuit breaker, rated 630 A at 50 °C with a MicroLogic 2.0 A electronic trip unit. It's a 3-pole, manually operated unit built for distribution duty in fixed-mount, backplate installations.

Trip unit and protection logic

The MicroLogic 2.0 A provides L (long-time overload) and I (instantaneous short-circuit) protection curves. This is an electronic trip unit, so you get adjustable thermal memory (20 mn) that keeps the breaker from nuisance-tripping on repeated inrush — a real help when starting motor loads or feeding transformers that hit the thermal curve on re-close. The LCD display and ammeter function let you read load current directly on the face, which saves a clamp-meter walk for troubleshooting.

Physical fit in the panel

Fixed-mount on a backplate, front connections both top and bottom. The 210 mm width, 327 mm height, and 147 mm depth are the numbers to check against your enclosure's gland-plate area and bus-bar takeoff pitch (70 mm between poles). IK07 impact rating means it takes a knock from a dropped tool without cracking the LCD.

Frequently asked questions

What are the key ratings of C063H32AFM?

630 A rated current at 50 °C, 3-pole, MicroLogic 2.0 A electronic trip unit with L and I protection. Breaking capacity is 70 kA Icu at 415 V AC (50/60 Hz), with higher ratings at lower voltages up to 85 kA at 220/240 V AC.

What compliance standards does this breaker meet?

It is designed and tested to EN/IEC 60947-2 for low-voltage switchgear and controlgear. Overvoltage category III, pollution degree 3, IP40, IK07.

Where can I buy C063H32AFM?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit a request for quote to confirm current availability and pricing.

MPN
C063H32AFM