Skip to main content
Schneider Electric C063H350FM — Miniature Circuit Breakers (MCB)

Schneider Electric C063H350FM ComPacT NS 630A, 70kA 415V AC

MPNC063H350FM
Active

Schneider Electric ComPacT NS new generation, C063H350FM, 3P 630A circuit breaker with MicroLogic 5.0 electronic trip unit, 70 kA Icu at 415 V AC, manually operated, fixed mount.

$3,340.96Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063H350FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063H350FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063H350FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063H350FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063H350FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063H350FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063H350FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The Schneider Electric C063H350FM is a ComPacT NS new generation 3-pole circuit breaker rated 630 A at 50 °C, fitted with a MicroLogic 5.0 electronic trip unit.

The C063H350FM's Icu curve spans 85 kA at 240 V AC down to 42 kA at 690 V AC, all per IEC 60947-2. Category B utilisation means it is certified for selectivity under short-circuit conditions, not just cable protection.

Trip unit and protection

MicroLogic 5.0 provides LSI protection: long-time overload (L), short-time short-circuit (S) with adjustable delay for zone-selective interlocking, and instantaneous (I). The electronic trip unit includes thermal memory with a 20-minute reset curve — after a trip, the breaker remembers the thermal state, so reclosing into a still-hot conductor does not mask an overload condition. Four red LEDs indicate fault type; one yellow LED signals overload pre-alarm.

Fixed-mount on a backplate, 210 mm wide × 327 mm high × 147 mm deep. Front connections on both line and load sides simplify busbar layout in a distribution panel. IP40 front face keeps tools and fingers out; IK07 impact rating handles incidental contact during panel work.

Frequently asked questions

What is C063H350FM's breaking capacity at 415 V AC?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, which is the H breaking capacity code for this frame.

What trip unit does the C063H350FM use?

A MicroLogic 5.0 electronic trip unit with LSI protection (long-time, short-time, instantaneous) and thermal memory.

Where can I buy C063H350FM and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
C063H350FM