Skip to main content
Schneider Electric C063H32EFM — Miniature Circuit Breakers (MCB)

C063H32EFM ComPacT NS 630A MCCB, 70kA 415V, MicroLogic 2.0 E

MPNC063H32EFM
Active

Schneider Electric ComPacT NS new generation, C063H32EFM, 3P 630A MCCB with MicroLogic 2.0 E electronic trip unit, 70 kA Icu at 415 V AC, fixed mount, IP40.

$2,501.54Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063H32EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063H32EFM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063H32EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063H32EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063H32EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063H32EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063H32EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The C063H32EFM is a 3-pole ComPacT NS630b...1600 new generation moulded-case circuit breaker from Schneider Electric, rated 630 A at 50 °C with an electronic MicroLogic 2.0 E trip unit. This is a distribution-device application (Category B utilisation), so it's built to coordinate with downstream breakers for selective tripping rather than just clearing a fault in isolation.

Trip curve and diagnostics you can read at a glance

The MicroLogic 2.0 E provides L (long-time overload) and I (instantaneous short-circuit) protection. It includes a 20-minute thermal memory so the breaker remembers prior heating events — critical for motor-starting or cyclic loads where nuisance tripping on a hot restart is a real risk. The front-panel LCD display shows metering and energy data, and four red LEDs flag the fault type while a yellow LED signals overload. No laptop needed to read what happened; the local signalling tells you at the panel door whether it was a sustained overload or a bolted fault that dropped the line.

This is a fixed-mount breaker — backplate-mounted, 327 mm high, 210 mm wide, 147 mm deep, with a 70 mm connection pitch. IK07 impact rating handles the occasional dropped tool during commissioning. Pollution degree 3 (IEC 60947) means it's rated for conductive environments typical in industrial switchgear, not just clean HVAC closets. The manually operated control with LCD display sits behind the door, so operators see status without opening the panel.

Frequently asked questions

What is C063H32EFM's breaking capacity at 415 V?

The 'H' breaking capacity code means 70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 220/240 V it's 85 kA Icu.

Where can I buy C063H32EFM?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for C063H32EFM?

The breaker is certified to EN/IEC 60947-2. Standard Schneider documentation includes the IEC declaration of conformity; specific RoHS/REACH declarations are available on request through the supply channel.

MPN
C063H32EFM