Skip to main content
Schneider Electric C063H320FM — Miniature Circuit Breakers (MCB)

Schneider Electric C063H320FM ComPacT NS 630A 3P MCCB, 70kA

MPNC063H320FM
Active

Schneider Electric ComPacT NS new generation, C063H320FM, 3P 630A MCCB with MicroLogic 2.0 electronic trip unit, 70 kA Icu at 415 V AC, fixed mount.

$1,501.57Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063H320FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063H320FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063H320FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063H320FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063H320FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063H320FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063H320FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The C063H320FM is a Schneider Electric ComPacT NS new generation 3-pole MCCB rated 630 A at 50 °C with a MicroLogic 2.0 electronic trip unit. The 85 kA at 240 V AC is relevant for 208/240 V panelboards in North American installs. The electronic trip unit provides L (long-time overload) and I (instantaneous short-circuit) protection, with a 20-minute thermal memory that prevents nuisance tripping on repeated inrush events — useful for motor or transformer feeders where the first start pulls the trip curve close to the threshold.

Fixed-mount on a backplate, front-connected both sides, with a 70 mm connection pitch. The 327 mm height, 210 mm width, and 147 mm depth fit standard ComPacT NS630b…1600 switchboard cutouts. IK07 covers low-energy impacts (0.5 J).

Certified to EN/IEC 60947-2, suitability for isolation per that standard — meaning it can be used as a visible-break disconnect when locked in the OFF position. Overvoltage category III for fixed-installation distribution. Electrical durability: 2000 cycles at full 690 V In, 5000 cycles at 440 V In. Mechanical durability: 10,000 cycles. These are lower than a contactor's life, but typical for a molded-case breaker that's operated only for isolation or fault clearing.

Frequently asked questions

Where can I buy C063H320FM and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to get current availability and pricing confirmed at quote time.

What is C063H320FM's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. That's the symmetrical short-circuit current the breaker can safely interrupt once at that voltage.

What trip unit does the C063H320FM use?

It uses a MicroLogic 2.0 electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection, with a 20-minute thermal memory.

What compliance documentation does Schneider provide for C063H320FM?

The breaker is certified to EN/IEC 60947-2 and is suitable for isolation per that standard. It carries IP40 and IK07 protection ratings. For specific RoHS/REACH/UL documentation, request the manufacturer's declaration of compliance with your RFQ.

MPN
C063H320FM