Schneider Electric C103TM016C — Miniature Circuit Breakers (MCB)

Schneider C103TM016C ComPacT NSX Trip Unit, 16A TM-D, 3P

MPNC103TM016C
Active

Schneider Electric ComPacT NSX100-250, TM-D thermal-magnetic trip unit, 16 A at 50 °C, 3 poles 3D, LI protection, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C103TM016C — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NSX100...250
Product/component typeTrip unit
Device applicationDistribution
C103TM016C — Ratings
ParameterValue
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz 750 V DC
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C103TM016C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
C103TM016C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C103TM016C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C103TM016C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C103TM016C is a TM-D thermal-magnetic trip unit for the ComPacT NSX100…250 range, rated 16 A at 50 °C. The instantaneous pickup is fixed at 190 A, while the long-time pickup (Ir) is adjustable from 0.7 to 1 x In.

IP40 front-of-panel protection handles finger-safe touch but isn't rated for washdown.

Coordination and selectivity notes

The fixed instantaneous pickup at 190 A (roughly 12 x In) gives a high magnetic threshold, which helps with short-circuit selectivity downstream. The long-time delay is fixed at 120…400 s at 1.5 x In and 15 s at 6 x Ir — that's the thermal memory curve for motor or transformer starting. For a 16 A feeder protecting a 10 A motor load, the 0.7–1 x In Ir adjustment lets you dial in the continuous protection without swapping trip units.

Frequently asked questions

What are the key ratings of C103TM016C?

16 A at 50 °C, 690 V AC / 750 V DC, 3 poles 3D, LI protection with fixed instantaneous pickup at 190 A and adjustable long-time pickup 0.7–1 x In.

What standards does C103TM016C comply with?

It is certified to EN/IEC 60947-2 for circuit-breaker performance and pollution degree 3 per IEC 60947-1.

Where can I buy C103TM016C?

Sourced and quoted to order against an RFQ through independent distribution — availability and current pricing confirmed at quote time.

MPN
C103TM016C