Skip to main content
Schneider Electric C103TM050C — Miniature Circuit Breakers (MCB)

C103TM050C ComPacT NSX TM-D Trip Unit, 50 A, 3P, Active

MPNC103TM050C
Active

Schneider Electric ComPacT NSX100...250, trip unit TM-D, thermal-magnetic, rating 50 A at 50 °C, 3 poles 3D, LI protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C103TM050C — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NSX100...250
Product/component typeTrip unit
Device applicationDistribution
C103TM050C — Ratings
ParameterValue
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz 750 V DC
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C103TM050C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
C103TM050C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C103TM050C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C103TM050C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Trip unit for ComPacT NSX100…250

The C103TM050C is a replacement / initial-fit trip unit for the Schneider Electric ComPacT NSX100 through NSX250 frame. The Ir long-time pickup is adjustable 0.7…1 x In; the Ii instantaneous pickup is fixed at 500 A. This means the unit can be dialed down to 35 A for a lightly loaded feeder, while the magnetic trip stays at 500 A regardless of the Ir setting — a common coordination point for downstream branch breakers.

The IP40 front face (IEC 60529) keeps tools and fingers out but is not sealed against hose-down — mount inside a cabinet for washdown areas.

Lifecycle status is Active per Schneider's current listing.

Integration note

Mounts into the ComPacT NSX100…250 fixed or plug-in base. The TM-D unit snaps into the breaker cradle without tools; verify the rotary dial on the front matches the Ir setting to the load schedule before closing the panel. The long-time delay (tr) is fixed — 120…400 s at 1.5 x In, 15 s at 6 x Ir — so no adjustment is possible for coordination curves beyond changing Ir.

Frequently asked questions

Where can I buy C103TM050C and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock or price figures are published here.

What is C103TM050C's listed range (ComPacT) on this component line?

It belongs to the ComPacT NSX100…250 range, specifically for the NSX100 and NSX160 frames (the TM-D trip unit is common to both).

What standards does C103TM050C comply with?

It is certified to EN/IEC 60947-2, the standard for low-voltage switchgear and controlgear. Pollution degree 3 per IEC 60947-1 also applies.

MPN
C103TM050C