Skip to main content
Schneider Electric C104TM063C — Miniature Circuit Breakers (MCB)

C104TM063C ComPacT NSX TM-D Trip Unit, 63 A, 4P 4D

MPNC104TM063C
Active

Schneider Electric ComPacT NSX100-250 series, TM-D thermal-magnetic trip unit, 63 A at 50 °C, 4 poles 4D, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C104TM063C — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NSX100...250
Product/component typeTrip unit
Device applicationDistribution
C104TM063C — Ratings
ParameterValue
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz 750 V DC
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C104TM063C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
C104TM063C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C104TM063C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C104TM063C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Trip unit for ComPacT NSX100-250

The C104TM063C is a TM-D thermal-magnetic trip unit for the Schneider Electric ComPacT NSX100-250 molded-case circuit breaker platform. Rated 63 A at 50 °C, it provides LI protection — thermal overload (L) via a fixed long-time delay and magnetic short-circuit (I) with a fixed instantaneous pickup of 500 A. The 4-pole 4D configuration protects all four poles, with the neutral on the left and neutral protection set to 1 x Ir.

The 500 A instantaneous pickup (roughly 8 x In) means magnetic trips occur above that threshold; below it, the thermal element handles overloads with a fixed delay of 120-400 s at 1.5 x In and 15 s at 6 x Ir. The long-time pickup is adjustable from 0.7 to 1.0 x In, giving some flexibility to match the downstream load without swapping the trip unit. Rated operational voltage is 690 V AC 50/60 Hz and 750 V DC, so it covers standard 400/480 VAC distribution and DC bus applications within that limit.

This trip unit snaps into ComPacT NSX100-250 breakers for distribution panels, motor control centers, and switchboards. Fixed mounting, 4-pole 4D with left-side neutral, Class II shock protection.

Frequently asked questions

What are the key ratings for C104TM063C?

The C104TM063C is a 63 A thermal-magnetic trip unit at 50 °C, 4 poles 4D, with a fixed instantaneous pickup of 500 A and adjustable long-time pickup from 0.7 to 1.0 x In. Rated operational voltage is 690 V AC and 750 V DC.

What standard does C104TM063C comply with?

The C104TM063C complies with EN/IEC 60947-2, the standard for low-voltage switchgear and controlgear circuit breakers.

Where can I buy C104TM063C?