Skip to main content
Schneider Electric C104TM100C — Miniature Circuit Breakers (MCB)

C104TM100C ComPacT NSX Trip Unit, TM100D, 100 A, 4P

MPNC104TM100C
Active

Schneider Electric ComPacT NSX series, trip unit C104TM100C, thermal-magnetic TM-D, 100 A at 50 °C, 4 poles 4D, LI protection, fixed instantaneous at 800 A.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C104TM100C — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NSX100...250
Product/component typeTrip unit
Device applicationDistribution
C104TM100C — Ratings
ParameterValue
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz 750 V DC
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C104TM100C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
C104TM100C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C104TM100C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C104TM100C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C104TM100C is a thermal-magnetic trip unit from the ComPacT NSX100...250 range, rated 100 A at 50 °C for distribution applications. It provides LI protection — thermal overload (L) with adjustable pickup from 0.7 to 1 x In, and magnetic short-circuit (I) fixed at 800 A. The 4-pole 4D configuration protects all poles including the neutral, with neutral protection set to 1 x Ir. The fixed thermal delay range (120–400 s at 1.5 x In, 15 s at 6 x Ir) means the long-time protection curve is pre-set within that window, not field-adjustable for delay.

Integration notes

Fits the ComPacT NSX100, NSX160, and NSX250 fixed-mount circuit breaker frames. The TM-D trip unit is field-replaceable — swap without removing the breaker from the panel. Neutral position is left; verify busbar or cable routing matches the 4D pole layout before assembly. IP40 front face, so the breaker panel door provides the environmental seal.

Frequently asked questions

What are the key ratings of the C104TM100C trip unit?

Rated 100 A at 50 °C, 4 poles 4D, LI protection with fixed instantaneous pickup at 800 A and adjustable thermal pickup from 0.7 to 1 x In. Rated operational voltage 690 V AC / 750 V DC per EN/IEC 60947-2.

Where can I buy the C104TM100C?

The C104TM100C is sourced and quoted to order against an RFQ through independent distribution channels. Contact us for current availability and pricing.

What compliance documentation is available for C104TM100C?

The trip unit is certified to EN/IEC 60947-2. Electrical shock protection Class II, pollution degree 3. No RoHS/REACH/UL specific statements are in the available documentation — verify with the manufacturer for your jurisdiction.

MPN
C104TM100C