TM-D trip unit for ComPacT NSX
It is rated 80 A at 50 °C, with 4 poles configured as 3D (three protected poles, no neutral protection).
Rating and protection settings
The long-time pickup (Ir) is adjustable from 0.7 to 1.0 x In, so you can dial the 80 A rating down to 56 A for cable protection or derating scenarios. The long-time delay (Tr) is fixed, with a characteristic of 120–400 s at 1.5 x Ir and 15 s at 6 x Ir — a standard thermal curve for distribution loads. Instantaneous pickup (Ii) is fixed at 640 A (8 x In), which gives good selectivity with downstream 16–32 A breakers on most panelboard feeds.
Voltage and environment
Rated operational voltage is 690 V AC 50/60 Hz and 750 V DC, so it covers 480Y/277 V and 600 V delta panels, plus DC bus applications up to 750 V. IP40 front face keeps tools and fingers out.