It's a 3-pole unit rated 40 A at 40 °C, with an integrated MicroLogic 4.2 electronic trip unit that provides overload (L), short-time short-circuit (So), instantaneous (I), and earth-leakage (R) protection. At 415 V AC the breaking capacity is 25 kA Icu, and at 440 V it's 20 kA Icu, all per IEC 60947-2. That standard certifies the breaker for industrial application, not just residential.
Deployment context
Mounts on a backplate in a distribution panel — horizontal or vertical orientation, flat on the back. The toggle control and front connections (both upside and downside) make it straightforward to wire in a panel layout. Mechanical durability is 50,000 cycles; electrical durability ranges from 50,000 cycles at 440 V at half rated current down to 10,000 cycles at 690 V at full rated current — so if you're switching near its limits frequently, factor that in.