Skip to main content
Schneider Electric C10B44V040

Schneider C10B44V040 ComPacT NSX 40A MCCB, 40kA Icu, MicroLo

MPN C10B44V040
Active

Schneider Electric, ComPacT NSX series, MCCB, 4P, 40 A, 40 kA Icu at 240 V AC, electronic MicroLogic 4.2 trip unit with integrated earth-leakage protection.

$1,108.12 – $2,008.80 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10B44V040 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10B44V040 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C10B44V040 is a ComPacT NSX100B molded-case circuit breaker, 4-pole, with a 40 A electronic MicroLogic 4.2 trip unit. This is the version with integrated earth-leakage protection — the 'V' in the code flags that. It's rated for distribution duty (category A) and carries a 40 kA Icu at 220/240 V AC, 25 kA at 415 V, and 20 kA at 440 V per IEC 60947-2.

Breaking capacity and what it means on your line

At 415 V — common for European industrial distribution — it's still 25 kA. That puts it in the 'B' breaking capacity class for 415 V systems. The MicroLogic 4.2 trip unit gives you L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous), and R (earth-leakage) protection curves. The earth-leakage is integrated, so you don't need a separate Vigi module or external RCD — saves a pole space and one wiring step.

Mounts on a backplate — no DIN rail here, so plan for bolt-down or screw-mount in the enclosure. The 4-pole version with the earth-leakage module is the same footprint as the standard 4P, so existing cutouts and busbar layouts carry over. Connection pitch is 35 mm, front-connected both top and bottom. Toggle handle for manual switching, with a rotary IΔn switch for the earth-leakage test/reset.

Durability and environment

Rated for 50,000 mechanical cycles and 30,000 electrical cycles at 440 V at full rated current. That's a solid service life for a distribution MCCB — expect it to outlast the panel refresh cycle in most plants.

MPN