Overview
Its thermal-magnetic TM-D trip unit provides LI protection (overload and short-circuit). The breaking capacity Icu is 18 kA.
Schneider lists the C10F1TM016 as an active, in-production part. The breaker carries an 18-month warranty.

Schneider ComPacT NSX C10F1TM016 molded case circuit breaker, 1-pole, 16 A, 18 kA breaking capacity, 277 V AC/DC, thermal-magnetic TM-D trip unit, fixed mount, front connection.
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Trip unit type | Thermal-magnetic |
| Main product or component type | Circuit breaker |
| Voltage | 277 V AC 50/60 Hz 250 V DC |
| Insulation voltage ui | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity | 18 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC conforming to IEC 60947-2 |
| IP rating | IP40 |
| Terminal pitch | 35 mm |
| Connection surface top | Front |
| Connection surface bottom | Front |
| Temp storage max | 85 °C |
| Temp storage min | -50 °C |
| Parameter | Value |
|---|---|
| Temp operating max | 70 °C |
| Temp operating min | -25 °C |
| Storage temperature | -50...85 °C |
| Pollution degree | class 3 |
| Depth | 86 mm |
| Width | 35 mm |
| Height | 161 mm |
| Electrical life cycles | 20000 cycles at 277 V In/2 10000 cycles at 277 V In |
| Mechanical life cycles | 20000 cycles |
| Application | Distribution |
| Operating temperature | -25...70 °C |
Its thermal-magnetic TM-D trip unit provides LI protection (overload and short-circuit). The breaking capacity Icu is 18 kA.
Schneider lists the C10F1TM016 as an active, in-production part. The breaker carries an 18-month warranty.