Specifications

C10F1TM030 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10F1TM030 — Ratings
ParameterValue
Rated current (In)30 A at 40 °C
Poles configuration1P
Breaking capacity18 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC conforming to IEC 60947-2
Rated service breaking capacity (Ics)18 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC conforming to IEC 60947-2
Rated operational voltage (Ue)277 V AC 50/60 Hz 250 V DC
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIV
C10F1TM030 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical durability (cycles)20000 cycles
C10F1TM030 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10F1TM030 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10F1TM030 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10F1TM030 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C10F1TM030 is a ComPacT NSX100F circuit breaker, 1-pole, with a TM-D thermal-magnetic trip unit rated 30 A at 40 °C. It breaks 18 kA Icu at 240 V AC (50/60 Hz) per IEC 60947-2, and 36 kA Icu at 250 V DC — that DC rating is unusual for a single-pole frame this size, useful if you are isolating a DC bus in a pitch-control cabinet or brake resistor circuit up-tower.

The 36 kA at 250 V DC is a separate rating — do not assume the same performance at 125 V DC or 48 V DC; consult the coordination tables if you are using it on a battery bank. The TM-D trip unit provides thermal overload protection (L) and magnetic short-circuit protection (I). At 30 A and 40 °C ambient, the thermal element tracks RMS current; below 40 °C it trips slightly slower, above 40 °C you must derate per the IEC 60947-2 thermal curve. The magnetic pickup is fixed at roughly 10× In (300 A), so it will not nuisance-trip on motor inrush unless the motor draws over 300 A locked-rotor.

Mounts on a backplate — not DIN-rail — so plan for screw-down fixing with the 35 mm pole pitch aligning to busbar or cable lugs. The 161 mm height and 86 mm depth fit a standard enclosure, but the 35 mm width per pole means a 1-pole unit occupies one module slot. Front connections top and bottom simplify busbar runs in a distribution board. The IK07 impact rating means it survives a 2 J hammer blow during panel assembly.

MPN