Skip to main content
Schneider Electric C10F2TM025 — Miniature Circuit Breakers (MCB)

Schneider Electric C10F2TM025 ComPacT NSX100F, 25 A, 18 kA 4

MPNC10F2TM025
Active

Schneider Electric ComPacT NSX100F, C10F2TM025, 25 A, 2-pole thermal-magnetic circuit breaker, 18 kA Icu at 415 V AC, TM-D trip unit, fixed mount.

$175.68Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10F2TM025 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10F2TM025 — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration2P
Breaking capacity36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2
Rated service breaking capacity (Ics)36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz 500 V DC
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10F2TM025 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical durability (cycles)20000 cycles
C10F2TM025 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10F2TM025 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10F2TM025 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10F2TM025 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The C10F2TM025 is a Schneider Electric ComPacT NSX100F circuit breaker with a 25 A TM-D thermal-magnetic trip unit, 2-pole, fixed-mount, rated for distribution duty per EN/IEC 60947-2. The 25 A rating at 40 °C sets the continuous current limit for the protected circuit — size your upstream conductor and downstream load to stay at or below that figure at the panel ambient. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection; the magnetic pickup is fixed, not adjustable, so verify the inrush of your load won't cause nuisance trips on motor or transformer starts. Breaking capacity: 36 kA Icu at 240 V AC, 18 kA at 415 V AC, 15 kA at 440 V, 10 kA at 525 V, and 5 kA at 690 V. On DC, 36 kA at 250 V DC (1 pole) and 36 kA at 500 V DC (2 poles in series). IP40 front face, IK07 impact resistance.

Lifecycle and sourcing — current production, quoted to order

Electrical durability is rated at 20,000 cycles at 277 V at In/2, and 10,000 cycles at 277 V at In. For a distribution breaker seeing infrequent switching (a few operations per month), that's effectively a lifetime rating.

Integration and mounting notes

Fixed-mount on a backplate. Dimensions: 161 mm high, 70 mm wide, 86 mm deep. Front connections top and bottom — no rear or plug-in option on this variant. Toggle control handle. Relative humidity 0–95 %. Overvoltage category III. Utilisation category A (not intended for frequent motor switching under load — that's category B or C territory). No earth-leakage protection integrated; add a Vigi module externally if ground-fault protection is needed.

Frequently asked questions

What is the breaking capacity of C10F2TM025 at 415 V?

18 kA Icu at 380/415 V AC 50/60 Hz, 1-pole configuration per IEC 60947-2. That's the breaking capacity code F rating.

MPN
C10F2TM025