Skip to main content
Schneider Electric C10F32D040 — Miniature Circuit Breakers (MCB)

Schneider Electric C10F32D040 ComPacT NSX100F, 40A, 85kA

MPNC10F32D040
Active

Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 3P, 40 A, MicroLogic 2.2 electronic trip unit, 85 kA Icu at 240 V AC.

$237.75Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10F32D040 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10F32D040 — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration3P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10F32D040 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10F32D040 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10F32D040 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10F32D040 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10F32D040 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range18...40 A
Trip unit protection functionsLSoI

Product details

The C10F32D040 is a Schneider Electric ComPacT NSX100F circuit breaker in the ComPacT range, fitted with a MicroLogic 2.2 electronic trip unit rated 40 A at 40 °C. It is a 3-pole unit built on the NSX100F frame, which means the breaker body and bus-bar connections are sized for 100 A maximum — the 40 A trip rating is set by the plug-in MicroLogic module, not the frame. That gives you headroom to re-trip to a higher rating later by swapping the trip unit, without pulling the breaker off the backplate. The electronic trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves. At 240 V AC it delivers 85 kA Icu; at 415 V AC it is 36 kA Icu; at 690 V AC it drops to 8 kA Icu.

Mounts on a backplate in any orientation — horizontal, vertical, or flat on the back. The 105 mm width, 161 mm height, and 86 mm depth fit standard ComPacT NSX cutouts; the 35 mm connection pitch aligns with common bus-bar systems. Front connections on both line and load sides simplify bus-bar routing and cable entry in a gland-plate layout. IP40 enclosure protection means it is suitable for clean indoor panels; IK07 impact resistance handles incidental tool contact during commissioning.

Frequently asked questions

What is the breaking capacity of C10F32D040 at 415 V AC?

At 380/415 V AC the C10F32D040 delivers 36 kA Icu per IEC 60947-2. At 480 V AC per UL 60947-4-1 it is 25 kA Icu.

What compliance documentation does Schneider Electric provide for C10F32D040?

The C10F32D040 is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries IP40 per IEC 60529, IK07 per IEC 62262, and is suitable for isolation per EN/IEC 60947-2. Pollution degree 3 per IEC 60664-1 and overvoltage category III are specified.

MPN
C10F32D040