Schneider Electric C10F32D100 — Miniature Circuit Breakers (MCB)

Schneider Electric C10F32D100 ComPacT NSX100F Circuit Breake

MPNC10F32D100
Active

Schneider Electric ComPacT NSX series, NSX100F, 3P, 100 A at 40 °C, 36 kA Icu at 415 V AC, MicroLogic 2.2 electronic trip unit, IP40, current production.

$316.24 – $739.42Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10F32D100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10F32D100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration3P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10F32D100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10F32D100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10F32D100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10F32D100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10F32D100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSoI

Product details

The Schneider Electric C10F32D100 is a ComPacT NSX100F three-pole molded-case circuit breaker rated 100 A at 40 °C, carrying a 36 kA Icu breaking capacity at 415 V AC. It uses a MicroLogic 2.2 electronic trip unit with L, So, and I protection curves.

What the breaking capacity means for your panel

The breaker is rated Category A (no intentional short-time delay for selectivity), which is typical for distribution feeders and downstream branch protection.

This is a current-production part.

Mounts on a backplate — no DIN rail required. The 105 mm width fits a standard 3-pole MCCB footprint. Front terminals top and bottom simplify busbar and cable routing. Five accessory slots let you add shunt trips, auxiliary contacts, or a motor mechanism without removing the breaker. Operating altitude derating starts at 2000 m — above that, consult the thermal curve. The toggle control gives clear visual indication of tripped vs on/off status, and the local LED signaling (green for ready, red/orange for overload) helps during commissioning and fault finding.

Frequently asked questions

What is the breaking capacity of C10F32D100 at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That's the F breaking capacity code on the NSX100F.

What trip unit does C10F32D100 use?

It uses a MicroLogic 2.2 electronic trip unit with L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection. The trip rating is 100 A at 40 °C.

What compliance documentation does Schneider provide for C10F32D100?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries IP40 and IK07 protection ratings, pollution degree 3 per IEC 60664-1, and overvoltage category III. It is suitable for isolation per EN/IEC 60947-2.

MPN