Specifications

C10F44B100 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10F44B100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (operating cycles)50000 cycles
C10F44B100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX100F
C10F44B100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10F44B100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10F44B100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C10F44B100 is a ComPacT NSX100F molded-case circuit breaker, 4-pole, rated 100 A at 40 °C with an electronic MicroLogic 4.2 AB trip unit. The 4.2 AB trip gives you L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection all in one device, so you cover both overcurrent and ground-fault from a single breaker. This is a Category A breaker (no intentional short-time delay for selectivity with downstream devices), so it's suited for feeder duty where you need fast clearing rather than cascaded coordination.

The C10F44B100 delivers 85 kA Icu at 240 V AC, 36 kA at 415 V, 35 kA at 440 V, and 22 kA at 525 V AC. At 480 V it is rated 25 kA Icu per UL 60947-4-1.

Front-connect both top and bottom, which keeps wiring accessible in a panel. The 4-pole format with neutral on the left is standard for European distribution.

Frequently asked questions

What is the breaking capacity of C10F44B100 at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That's the 'F' breaking capacity code — sufficient for most commercial and light industrial distribution panels.

What protection functions does the MicroLogic 4.2 AB trip unit provide?

It covers L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage protection) — all integrated into the electronic trip unit.