Skip to main content
Schneider Electric C10F44V040 — Residual Current Breakers (RCCB/RCBO)

Schneider C10F44V040 ComPacT NSX MCCB, 4-pole, 40 A, 440 V AC, 85 kA

MPNC10F44V040
Active

Schneider C10F44V040 Compact Nsx, New Generation — now discontinued. Supplied from remaining channel stock; full specifications, lifecycle and same-series options are below.

$1,127.44 – $2,069.28Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

C10F44V040 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10F44V040 — Electrical Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (operating cycles)50000 cycles
C10F44V040 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX100F
C10F44V040 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10F44V040 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10F44V040 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Overview

It uses a MicroLogic 4.2 electronic trip unit and is configured as a 4-pole unit with fixed mounting and toggle control. This part is in active production.

MPN
C10F44V040